3 manual initialization of linear actuator – Siemens SIPART PS2 6DR52xx User Manual

Page 76

Advertising
background image

Preparing for Operation

76

SIPART PS2 Manual

A5E00074631--06

3.6.3

Manual initialization of linear actuator

The positioner can be initialized with this function without the actuator

being driven hard against the limit stop. The start and end positions of

the travel are set manually. The other initialization steps (optimization

of the control parameters) run automatically as in automatic initializa-

tion.

1.

Make preparations as described in chapter 3.6.1, page 73 for

linear actuator. In particular, make sure by manually driving the whole

travel that the displayed potentiometer setting moves in the permis-

sible range between P5.0 and P95.0.

Press the operation mode key

for longer than 5 s. This brings

you to the Configuration mode.

Display:

3.

Switch to the second parameter by pressing the operation key
briefly. One of the following displays appears:

or

.

NOTE
It is vital that this value corresponds to the setting of the transmission

ratio selector (33_ or 90°).

4.

Switch on to the following display

with the operation mode key:

You only need to set this parameter if you want to have the total

stroke in mm displayed at the end of the initialization phase. To do

this, select the same value in the display to which you have set

the carrier pin to the scale on the lever or the next highest position

in intermediate positions.

Manual initializa-

tion procedure in

linear actuator

Advertising
This manual is related to the following products: