HRX-OM-J049-A

Chapter 3 Transport and Installation

HRG010-W HRG015-W

3.2 Installation

1st edition : Aug. 2006
Rev. A: May. 2007

3-9

3.2.5 Electrical wiring

„

Power supply cable and GFCI breaker

Select a cable for power supply and GFCI breaker corresponding to the model no.
provided in the following table.

Table 3-2 Cable for Power Supply and Current Leakage

Item

HRG010-W

HRG015-W

Size

4- core 8 mm

2

4- core 14 mm

2

Power cable

Round crimp contact size

8 - 4S

14 - 5S

Size

6- core 0.75 mm

2

Signal cable

Y-shaped crimp contact size

1.25Y - 3

Capacity of GFCI breaker

*

40A 60A

* Use the breaker with current sensitivity of 30mA at minimum.

z

Only qualified personnel are allowed to install wiring.

z

Be sure to disconnect the power for safety. Wiring installation with

the unit energized is strictly prohibitted.

z

Use the specified cables. Properly apply strain relief to prevent an

external force from being exerted on the terminals. Poor or loose
connection can cause electrical shock, heat spots, or fire.

z

Supply the power to the unit from a reliable power source (without

surge or sag voltage).

z

Be sure to use a GFCI breaker to prevent an electrical shock and

burnt compressor motor. The breaker with adequate capacity of
current leakage and load should be selected in accordance with “7.1
Standard Specifications”.

z

Ensure that the power supply meets the specification of the unit.

z

Always establish a ground for safety.

z

Do not connect the ground to a water line, gas pipe or lighting

conductor.

z

Do not branch off the wiring to make multiple circuits. Potential hot

spots or fire may occur if disregarded.

z

Do not modify the electrical wiring. Incorrect wiring can cause an

electrical shock and fire. Failure to do so will void any warranty.

z

The set value of the safety device must not be changed. Changing

the set value can cause unit failure and fire.

Advertising