Chapter 6 Unit Maintenance

HRG010-W HRG015-W

6.1 Control of Water Quality

1st edition : Aug. 2006
Rev. A: May. 2007

6-1

Chapter 6 Unit Maintenance

6.1 Control of Water Quality

Table 6-1 Water quality standards for fresh water (tap water)

Substances

Facility water

spec.

Circulating fluid spec.

pH (25°C)

6.5 to 8.2

6.0 to 8.0

Electrical conductivity (25°C) (µs/cm)

100

(*1)

to 800

100

(*1)

to 300

(*2)

Chloride ion (mgCl-/L)

200 and below

50 and below

Sulfuric acid ion (mgSO

4

2-

/L)

200 and below

50 and below

Acid consumption (pH4.8) (mgCaCO

3

/L)

100 and below

50 and below

Total hardness (mgCaCO

3

/L)

200 and below

70 and below

Calcium hardness (mgCaCO

3

/L)

150 and below

50 and below

Ion silica (mgSiO

2

/L)

50 and below

30 and below

Iron (mgFe/L)

1.0 and below

0.3 and below

Copper (mgCu/L)

0.3 and below

1.0 and below

Sulfide ion (mgS

2-

/L) Not

detected

Ammonium ion (mgNH

4

+

/L)

1.0 and below

0.1 and below

Residual chlorine (mgCl/L)

0.3 and below

0.3 and below

Free carbon dioxide (mgCO

2

/L)

4.0 and below

4.0 and below

Standard

Filtering (μm)

5 and below

* Refrigeration and Air Conditioning Equipment Water Quality

Guideline JRA-GL-02-1994

(*1) Electrical conductivity: Min. 100[μS/cm]
(*2) 0.003 to 0.01 if the unit of M[

Ω•cm] is used.

The circulating fluid used in this unit is fresh water (tap water). This
unit may be damaged when unpermitted fluids are used.
Potential fluid leak may occur if disregarded, which results in electric
shock and ground fault.
ONLY use fresh water (tap water) which satisfies water quality
standards as shown in the table below.

If the periodic inspection finds a nonconforming substance in the
facility water, wash the tank and the cirulating circuit, and replace the
water in the tank. Water will evaporate, and impurities will build up.
Even if no abnormal event occurs, it is recommended to replace the
water in the tank once every three months. Refer to section "6.2
Inspection and Cleaning" for the periodic inspection.