HRX-OM-J049-A

Chapter 5 Error Message and Troubleshooting

HRG010-W HRG015-W

5.3 Alarm Reset (Alarm Lamp OFF)

1st edition : Aug. 2006
Rev. A: May. 2007

5-5

3.

Press the Reset switch [RS] (yellow button) on the control panel and make sure that the
alarm lamp goes out.

Fig. 5-4 Location of Reset Switch [RS] (Yellow Button)

„

When the alarm lamp goes out by performing steps 1. to 3.

4.

Attach the front panel.

5.

Implement system startup and shutdown according to “Chapter 4 Startup and Shutdown”.

„

When the alarm lamp remains on after performing steps 1. to 3.

6.

Press the reset button of each detector in the electrical unit.

7.

Follow step 3. to press the Reset switch [RS] (yellow button).

The alarm lamp goes out accordingly.

8.

Implement system startup and shutdown according to “4.3 Unit Startup and Shutdown”.

Fig. 5-5 Location of Reset Switch [RS] (Yellow Button)

Control panel

Reset switch [RS]
(yellow button)

Front

Front

Pump overload reset button
(blue button)

Compressor overload reset
button (blue button)

Facility water supply suspension
reset button (red button)