Chapter 7 documents, 1 standard specifications – Sierra Monitor Corporation HRG015-W User Manual

Page 59

Advertising
background image

HRX-OM-J049-A

Chapter 7 Documents

HRG010-W HRG015-W

7.1 Standard Specifications

1st edition : Aug. 2006
Rev. A: May. 2007

7-1

Chapter 7 Documents

7.1 Standard Specifications

Table 7-1 Standard Specifications (1/2)

Item

HRG010-W

HRG015-W

Rated ambient temp.

32°C (5 to 40°C)

In

st

alla

tio

n

Operat

ing

env
ironm
ent

Humidity range

45 to 75%RH (No condensation)

Fluid used

Circulating fluid/fresh water (tap water) or fluids resistant to corrosion of a wetted surface

(such as SUS304 and PVC)

Rated capacity of tank

40L

50L

Supply voltage

3-phase AC200(50Hz), AC200 to 220V (60Hz)

Recommended earth

leakage breaker capacity,

Sensitivity current

40A, 30mA

60A, 30mA

Rated power consumption

3.2/3.8 - 3.8 kW

4.7/5.8 - 5.8 kW

Rated operating current

12.0/12.5 - 12.5A

18.0/19.0 – 19.0A

Rated consumption

electric energy

3.2/3.8 - 3.8 kWh/h

4.7/5.8 - 5.8kWh/h

Facility water

Supply temp.: 25°C (5 to 32°C),

Flow rate: Max. 33/34L/min,

IN/OUT differential pressure: Max.

0.25/0.2MPa,

Max. supply press.: 0.3 to 0.4MPa, Exhaust

heat: Approx. 16W

Supply temp.: 25°C (5 to 32°C),

Flow rate: Max. 38/40L/min,

IN/OUT differential pressure: Max. 0.25/0.2MPa,

Max. supply press.: 0.3 to 0.4MPa, Exhaust heat:

Approx. 23W

Input

Start/stop command

signal

Remote operation starts upon application of DC24V and 8 mA, and stops at DC0V.

Rated temp. / accuracy of

circulating fluid

20±1.0°C (only under given load condition)

Temp. range of circulating

fluid

5 to 35°C

Rated cooling capacity

10.0/11.0 kW

(50/60 Hz, 20°C at outlet, 37/49L/min of flow)

14.5/16.5kW

(50/60 Hz, 20°C at outlet, 42/54L/min of flow)

Rated heating capacity

- (1.1kW of pump motor output only)

- (0.75kW of pump motor output only)

Pumping capacity

Max. head: 50/50m (50/60Hz, 0/0L/min of flow, 0.49/0.49MPa of supply pressure)

Rated flow

37/49L/min

(50/60Hz, 25/25m of the max. head,

0.29/0.33MPa of supply pressure)

42/54L/min

(50/60Hz, 25/25m of the max. head,

0.28/0.31MPa of supply pressure)

Max. flow rate

48/60L/min

(50/60Hz, 0/0m of the max. head,

0.08/0.12MPa of supply pressure)

54/65L/min

(50/60Hz, 0/0m of the max. head,

0.05/0.09MPa of supply pressure)

Op. signal

Relay contact ( AC250V of contact capacity, 1A, resistance load. Contact closes during operation,

and contact opens during stop and during power-off.)

Out
put

Output

signal Emergency stop

signal

Relay contact (AC250V of contact capacity, 1A, resistance load. Contact closes while alarm light

remains OFF and during power-off, and contact opens while alarm light remains ON.)

Temperature control

Combined use of temperature control through compressor operation (ON/OFF) and capacity

control through solenoid valve control (ON/OFF)

Operation panel

7segment digital display, capable of display in 0.1°C increments

PV (operating temp.): 4-digit display in green, SV (set temp.): 4-digit display in red

Other display lamps: ALARM1 to 3 individual display in the event of an error)

Refrigerant high pressure

gauge

Range: -0.1 to 3.5 MPa

Refrigerant pressure

gauge

Range: 0 to 1.0 MPa

D

isp

la

y

Level indicator

SMC Ø-10 tube TU1065C (transparent)

Advertising