background image

HRX-OM-J049-A

Chapter 4 Startup and Shutdown

HRG010-W HRG015-W

4.2 Preparation for startup

1st edition : Aug. 2006
Rev. A: May. 2007

4-3

4.2.3 Additional

water

supply

„

[TS] switch (pump manual operation switch)

This unit has the [TS] switch (pump manual operation switch) to purge air from the
circulating fluid circuit at initial startup. Remove the front panel, and purge air
according to the procedures given below.

Fig. 4-3 [TS] switch (pump manual operation switch)

1.

Press the [TS] switch for several seconds, monitoring the fluid level gauge.

Air is purged from the pipe, and the fluid level is lowered.

z

The [ALARM1] lamp comes on (error). The lamp goes out with the press of the [RS] switch after the
circulating fluid reaches the range specified on the level indicator.

z

See “Chapter 5 Error Message and Troubleshooting” for error messages.

Fig. 4-4 Location of Reset Switch (Yellow Button)

2.

Supply the circulating fluid again according to section “3.2.7Supply of circulating fluid”.

[TS] switch
(green)

Front

Control panel

Reset SW [RS]
(yellow button)

Front

If leakage occurs due to faulty piping including an opened fitting of eternal piping,
stop manual operation of the pump and fix the leak.