HRX-OM-J049-A
Chapter 5 Error Message and Troubleshooting

5.2 Troubleshooting

HRG010-W HRG015-W

1st edition : Aug. 2006

Rev. A: May. 2007

5-2

5.2 Troubleshooting

See “5.3 Alarm Reset” for error recovery.

Table 5-2 Troubleshooting

Alarm reset

Error

Cause

Remedies

Detector

HRG

No power is supplied.

With the switch in its ON position, supply the

main power. Only qualified personnel are
allowed for power wiring.

Open phase

Supply 3-phase power (R- and
S-phases).Only qualified personnel are

allowed for power wiring.

-

Overcurrent

Request for service. Turn ON the breaker.

Power error

Ground fault

Request for service. Turn ON the breaker.

Manual reset

*1)

-

Start-up
failure

Low voltage

Supply a rated voltage. Only qualified
personnel are allowed for power wiring.

- -

Reverse of
pump and

compressor

Incorrect phase
sequence of power

wiring

Rewire the power cable for two of three
phases (phase sequence). Only qualified

personnel are allowed for power wiring.

Tank fluid
level drop

Inadequate quantity of
the fulid in the tank, or

drop in the tanked fluid

level

Replenish the circulating fluid (fresh water).

Auto reset

*2)

Manual reset

(yellow

button)

*3)

Suspension of
facility water
supply

Supplied facility water
falls short of its specified
volume.

Press the reset button of the high pressure
cutoff switch.
Supply facility water standing at 5 to 32°C.

Manual reset

(red button)

*1)

Manual reset

(yellow
button)

*3)

Abnormal rise in fluid

supply pressure

Press the reset button of the pump

electromagnetic switch (MS1). Adopt a pipe
size suitable for circulating fluid flow, or,

adjust the opening of the manual relief valve.

Pump
overload

Failure in the pump

motor

Request for service.

Manual reset

(blue button)

*1)

Manual reset

(yellow
button)

*3)

Abnormal rise in ambient
temperature

Improve ambient conditions to provide
ventilation and exhaust heat. Keep the unit

out of direct sunlight and radiant heat.

Excessive calorific value

of the chiller

Reduce a calorific value output from your unit.

Refrigerant leak

Request for service.

Compressor error

Request for service.

Failure in the
electromagnetic switch Request for service.

Other errors in the
refrigerating circuit

Request for service

High temp. of
supplied fluid

Failure in the temp.

controller

Request for service.

Auto reset

*2)

Manual reset

(yellow

button)

*3)

Excessive calorific value

of the chiller

Press the [RESET] button of the compressor

electromagnetic switch (MS2). Reduce a
calorific value output from your system.

Compressor

overload

Failure in the

compressor motor

Request for service.

Manual reset

(blue button)

*1)

Manual reset

(yellow
button)

*3)

*1)

The recovery from an error capable of manual alarm reset takes place with the use of the switch and reset

button after the cause (such as fluid level drop or abnormal temperature) is eliminated.

*2)

The recovery from an error capable of automatic alarm reset takes place when the cause (such as fluid level

drop or abnormal temperature) is eliminated after waiting period.

*3)

With the tripped detector located, be sure to press the [RESET] button (yellow button) of the system electrical
unit after the elimination of the error cause. The alarm lamp goes out that enables the unit to resume.