Chapter 5 error message and troubleshooting, 1 error message – Sierra Monitor Corporation HRG015-W User Manual

Page 45

Advertising
background image

HRX-OM-J049-A

Chapter 5 Error Message and Troubleshooting

HRG010-W HRG015-W

5.1 Error Message

1st edition : Aug. 2006
Rev. A: May. 2007

5-1

or

or

or

or

[POWER] LED

[ALARM 1] LED

[POWER] LED

[ALARM 2] LED

[ALARM 3] LED

Chapter 5 Error Message and

Troubleshooting

5.1 Error Message

This product stops when an error is detected.

Table 5-1 shows the LED conditions (ON/OFF) and signal output in the event of
the error.

Fig. 5-1 Control Panel

Table 5-1 Error Message

LED

(z: Off, {: On)

Alarm

Setting

range

System

status

POWER

RUN ALARM1 ALARM2 ALARM3

Operation

signal

output

Error stop

signal

output

Power error

-

Stopped

{

{

{

{

{

Open

contact

Closed

contact

Start-up failure

-

Stopped Greenz

{

{

{

{

Closed

contact

Closed

contact

Reverse of pump

and compressor

- Stopped Greenz

{

Redz

{

{

Open

contact

Open

contact

Tank fluid level

drop

Lower limit of

fluid level in

the tank

Stopped Greenz

{

Redz

{

{

Open

contact

Open

contact

Suspension of

facility water

supply

- Stopped Greenz

{

Redz

{

{

Open

contact

Open

contact

Pump overload

-

Stopped Greenz

{

{

Redz

{

Open

contact

Open

contact

High temp. of

supplied fluid

40°C and

over

Stopped Greenz

{

{

Redz

{

Open

contact

Open

contact

Compressor

overload

- Stopped Greenz

{

{

{

Redz

Open

contact

Open

contact

Advertising