1-13. Example of Tubing Size Selection and Refrigerant Charge Amount

Additional refrigerant charging

Based on the values in Tables 1-9, 10, 11, 12 and 15, use the liquid tubing size and length, and calculate the amount of additional

refrigerant charge using the formula below.

= 3.93

× (a) + 2.78 × (b) + 1.99 × (c) + 1.38 × (d) + 0.602 × (e) + 0.279 × (f)

(a) : Liquid tubing

Total length of ø7/8" (ft.)

(d) : Liquid tubing

Total length of ø1/2" (ft.)

(b) : Liquid tubing

Total length of ø3/4" (ft.)

(e) : Liquid tubing

Total length of ø3/8" (ft.)

(c) : Liquid tubing

Total length of ø5/8" (ft.)

( f ) : Liquid tubing

Total length of ø1/4" (ft.)

● Charging procedure

Be sure to charge with R410A refrigerant in liquid form.

1. After performing a vacuum, charge with refrigerant from the liquid tubing side. At this time, all valves must be in the “fully

closed” position.

2. If it was not possible to charge the designated amount, operate the system in Cooling mode while charging with refrigerant

from the gas tubing side. (This is performed at the time of the test run. For this, all valves must be in the “fully open” position.

However if only one outdoor unit is installed, a balance tube is not used. Therefore, leave the valves fully closed.)

Charge with R410A refrigerant in liquid form.

With R410A refrigerant, charge while adjusting the amount being fed a little at a time in order to prevent liquid refrigerant from

backing up.

● After charging is completed, turn all valves to the “fully open” position.
● Replace the tubing covers as they were before.

Required additional
refrigerant charge (oz)

CAUTION

1. R410A additional charging absolutely must

be done through liquid charging.

2. The R410A refrigerant cylinder has a gray

base color, and the top part is pink.

3. The R410A refrigerant cylinder includes a

siphon tube. Check that the siphon tube is

present. (This is indicated on the label at the

top of the cylinder.)

4. Due to differences in the refrigerant, pres-

sure, and refrigerant oil involved in installa-

tion, it is not possible in some cases to use

the same tools for R22 and for R410A.

1

2

3

4

LA

LB

LC

A

B

Outdoor unit

09053
model

09053
model

48 model

48 model

48 model

36 model

Example:

● Example of each tubing length

Main tubing

Distribution joint tubing

LA = 131 ft.

Outdoor side

Indoor side

LB = 16 ft.

A = 7 ft.

1 = 98 ft.

LC = 16 ft.

B = 7 ft.

2 = 16 ft.

3 = 16 ft.

4 = 65 ft.

Balance tube

Liquid tube

Gas tube

Use a flathead screwdriver and
open by turning the part with the
screw groove to the right,
from “–” to “|”.

Use a flathead screwdriver and
open by turning the part with the
screw groove to the right,
from “–” to “|”.

Use a hex wrench (width 5/32 inch)
and turn to the left to open.