Sanyo R410A User Manual

Page 34

Advertising
background image

34

A

Fig. 3-41

Air bleed valve

Fig. 3-43

Fig. 3-42

0 – 45°

11-13/16 in. or less

33-15/32 in. or less

* Length of supplied drain hose = 9-27/32 in.

Uphill slope

Fig. 3-44

Support

bracket

CAUTION

3-11. Checking the Drainage

After wiring and drain piping are completed, use the
following procedure to check that the water will drain
smoothly. For this, prepare a bucket and wiping cloth to
catch and wipe up spilled water.

(1) Connect power to the power terminal board (R, S

terminals) inside the electrical component box.

(2) Pour about 0.2 gal of water into the drain pan using a

siphon pump through the air outlet grille. (Fig. 3-45)

(3) Short the check pin (CHK) on the indoor control board

and operate the drain pump. Check the water flow
through the transparent drain pipe and see if there is any
leakage.

(4) When the drainage check is complete, open the check

pin (CHK) and remount the insulator.

CAUTION

CAUTION

Be careful since the fan will start
when you short the pin on the indoor
control board.

The bottom drain port is for use only
during test runs and servicing
inspections. Do not connect the drain
pipe to the bottom drain port.

water (0.2 gal)

Drainage check

Drain tube
connection
(transparent)

Discharge port

Fig. 3-45

Do not install an air bleeder as this may cause water
to spray from the drain pipe outlet. (Fig. 3-41)

In cases where it is necessary to raise the height of
the drain piping, the drain piping can be raised to a
maximum height of 33-15/32" above the bottom
surface of the ceiling. Under no conditions attempt to
raise it higher than 33-15/32" above the bottom
surface of the ceiling. Doing so will result in water
leakage. (Fig. 3-42)

Do not use natural drainage.

Do not install the pipe with an upward gradient from
the connection port. This will cause the drain water
to flow backward and leak when the unit is not
operating. (Fig. 3-43)

Do not apply force to the piping on the unit side when
connecting the drain pipe. The pipe should not be
allowed to hang unsupported from its connection to
the unit. Fasten the pipe to a wall, frame, or other
support as close to the unit as possible. (Fig. 3-44)

Provide insulation for any pipes that are run indoors.

07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 34