68

Fig. 7-4

(4) Do a leak test of all joints of the tubing (both indoor and

outdoor) and both gas and liquid service valves. Bub-

bles indicate a leak. Wipe off the soap with a clean cloth

after a leak test.

(5) After the system is found to be free of leaks, relieve the

nitrogen pressure by loosening the charge hose con-

nector at the nitrogen cylinder. When the system pres-

sure is reduced to normal, disconnect the hose from the

cylinder.

Evacuation

(1) Attach the charge hose end described in the preceding

steps to the vacuum pump to evacuate the tubing and

indoor unit. Confirm that the “Lo” knob of the manifold

valve is open. Then, run the vacuum pump. The opera-

tion time for evacuation varies with the tubing length and

capacity of the pump. The following table shows the

amount of time for evacuation:

Manifold valve

Pressure
gauge

Lo

Hi

Vacuum pump

Outdoor unit

Close

Open

Liquid
tube

Gas
tube

Balance
tube

Close

Open

Close

Open

Required time for evacuation

when 30 gal/h vacuum pump is used

If tubing length is

If tubing length is

less than 49 ft.

longer than 49 ft.

45 min. or more

90 min. or more