Sanyo R410A User Manual

Page 67

Advertising
background image

67

Fig. 7-1

Fig. 7-2

Fig. 7-3

7. AIR PURGING

Air and moisture in the refrigerant system may have

undesirable effects as indicated below.

● pressure in the system rises
● operating current rises
● cooling (or heating) efficiency drops
● moisture in the refrigerant circuit may freeze and block capillary

tubing

● water may lead to corrosion of parts in the refrigerant system

Therefore, the indoor unit and tubing between the indoor and

outdoor unit must be leak tested and evacuated to remove any

noncondensables and moisture from the system.

Air Purging with a Vacuum Pump (for Test Run) Preparation

Check that each tube (both liquid and gas tubes) between the

indoor and outdoor units have been properly connected and all

wiring for the test run has been completed. Remove the valve caps

from both the gas and liquid service valves on the outdoor unit.

Note that both liquid and gas tube service valves on the outdoor

unit are kept closed at this stage.

Leak test

(1) With the service valves on the outdoor unit closed, remove the

5/16" flare nut and its bonnet on the gas tube service valve.

(Save for reuse.)

(2) Attach a manifold valve (with pressure gauges) and dry

nitrogen gas cylinder to this service port with charge hoses.

(3) Pressurize the system to no more than 469 psig (33 kgf/cm

2

G)

with dry nitrogen gas and close the cylinder valve when the

gauge reading reaches 469 psig (33 kgf/cm

2

G). Then, test for

leaks with liquid soap.

Manifold gauge

Outlet
Inlet

Vacuum pump

Manifold valve

Pressure
gauge

Lo

Hi

Charge hose

Outdoor unit

Close

Open

Liquid
tube

Gas
tube

Balance
tube

Nitrogen gas cylinder
(In vertical standing
position)

Close

Open

Close

Open

Cylinder
valve

CAUTION

CAUTION

To avoid nitrogen entering the

refrigerant system in a liquid state, the

top of the cylinder must be higher than

the bottom when you pressurize the

system. Usually, the cylinder is used in

a vertical standing position.

Use a manifold valve for air purging.

If it is not available, use a stop valve

for this purpose. The “Hi” knob of

the manifold valve must always be

kept closed.

07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 67

Advertising