2-3. Shield for Horizontal Exhaust Discharge

It is necessary to install an air-discharge chamber (field

supply) to direct exhaust from the fan horizontally if it is diffi-

cult to provide a minimum space of 7 ft. between the air-dis-

charge outlet and a nearby obstacle. (Fig. 2-8)

CAUTION

In regions with heavy snowfall,

the outdoor unit should be

provided with a solid, raised plat-

form and snow-proof ducting

(field supply). (Fig. 2-9)

2-4. Installing the Outdoor Unit in Heavy Snow

Areas

In locations where wind-blown snow can be a problem,

snow-proof ducting (field supply) should be fitted to the unit

and direct exposure to the wind should be avoided as much

as possible. (Fig. 2-10) The following problems may occur if

proper countermeasures are not taken:

● The fan in the outdoor unit may stop running, causing the

unit to be damaged.

● There may be no air flow.

● The tubing may freeze and burst.

● The condenser pressure may drop because of strong

wind, and the indoor unit may freeze.

2-5. Precautions When Installing in Heavy Snow

Areas

a) The platform should be higher than the maximum snow

depth. (Fig. 2-9)

b) The 2 anchoring feet of the outdoor unit should be used

for the platform, and the platform should be installed

beneath the air-intake side of the outdoor unit.

c) The platform foundation must be solid and the unit must

be secured with anchor bolts.

d) When installing on a roof subject to strong wind, coun-

termeasures must be taken to prevent the unit from

being overturned.

With snow-
proof ducting

(High platform)

Without snow-
proof ducting

(Without platform)

AVOID

Fallen snow

DO

Fig. 2-8

Fig. 2-9

Fig. 2-10

21

07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 21