Sanyo R410A User Manual

Page 64

Advertising
background image

64

Caution Before Connecting Tubes Tightly

(1) Apply a sealing cap or water-proof tape to prevent dust

or water from entering the tubes before they are used.

(2) Be sure to apply refrigerant lubricant to the matching

surfaces of the flare and union before connecting them

together. This is effective for reducing gas leaks.

(Fig. 6-4)

(3) For proper connection, align the union tube and flare

tube straight with each other, then screw in the flare nut

lightly at first to obtain a smooth match. (Fig. 6-5)

● Adjust the shape of the liquid tube using a tube bender

at the installation site and connect it to the liquid tubing

side valve using a flare.

Cautions During Brazing

Replace air inside the tube with nitrogen gas to

prevent copper oxide film from forming during the

brazing process. (Oxygen, carbon dioxide and Freon

are not acceptable.)

Do not allow the tubing to get too hot during

brazing. The nitrogen gas inside the tubing may

overheat, causing refrigerant system valves to

become damaged. Therefore allow the tubing to

cool when brazing.

Use a reducing valve for the nitrogen cylinder.
Do not use agents intended to prevent the formation

of oxide film. These agents adversely affect the

refrigerant and refrigerant oil, and may cause

damage or malfunctions.

6-2. Connecting Tubing Between Indoor and

Outdoor Units

(1) Tightly connect the indoor-side refrigerant tubing

extended from the wall with the outdoor-side tubing.

(2) To fasten the flare nuts, apply specified torque as at

right:

● When removing the flare nuts from the tubing

connections, or when tightening them after connecting

the tubing, be sure to use 2 monkey wrenches or

spanners as shown. (Fig. 6-6)

If the flare nuts are over-tightened, the flare may be

damaged, which could result refrigerant leakage and

cause in injury or asphyxiation to room occupants.

● For the flare nuts at tubing connections, be sure to use

the flare nuts that were supplied with the unit, or else

flare nuts for R410A (type 2). The refrigerant tubing that

is used must be of the correct wall thickness as shown in

the table at right.

Apply refrigerant
lubricant here and here

Fig. 6-4

Flare nut

Union

Fig. 6-5

Fig. 6-6

Indoor unit

Outdoor unit

Spanner

Torque wrench

1/32"
(0.8 mm)

1/32"
(0.8 mm)

1/32"
(0.8 mm)

5/128"
(1.0 mm)

over 5/128"
(1.0 mm)

Tube diameter

ш1/4" (ш6.35 mm)

ш3/8" (ш9.52 mm)

ш1/2" (ш12.7 mm)

ш5/8" (ш15.88 mm)

ш3/4" (ш19.05 mm)

Tightening torque,
approximate

120 – 160 lbs

·

inch

(140 – 180 kgf

·

cm)

300 – 360 lbs

·

inch

(340 – 420 kgf

·

cm)

430 – 530 lbs

·

inch

(490 – 610 kgf

·

cm)

590 – 710 lbs

·

inch

(680 – 820 kgf

·

cm)

870 – 1040 lbs

·

inch

(1000 – 1200 kgf

·

cm)

Tube thickness

Because the pressure is approximately 1.6 times higher

than conventional refrigerant pressure, the use of ordinary

flare nuts (type 1) or thin-walled tubes may result in tube

rupture, injury, or asphyxiation caused by refrigerant

leakage.

● In order to prevent damage to the flare caused by over-

tightening of the flare nuts, use the table above as a guide

when tightening.

● When tightening the flare nut on the liquid tube, use a

monkey wrench with a nominal handle length of 7-7/8 in.

07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 64

Advertising