Control wiring

(C) Inter-unit (between outdoor and

indoor units) control wiring

(D) Remote control wiring

(E) Control wiring for group control

(F) Inter-outdoor unit control wiring

AWG #18 (0.75 mm

2

)

AWG #18 (0.75 mm

2

)

AWG #18 (0.75 mm

2

)

AWG #18 (0.75 mm

2

)

Use shielded wiring*

Use shielded wiring

Use shielded wiring

Use shielded wiring

Max. 3,280 ft.

Max. 1,640 ft.

Max. 1,640 ft. (Total)

Max. 1,640 ft.

5. ELECTRICAL WIRING

5-1. General Precautions on Wiring

(1) Before wiring, confirm the rated voltage of the unit as

shown on its nameplate, then carry out the wiring

closely following the wiring diagram.

(2) Provide a power outlet to be used exclusively for each

unit, and a power supply disconnect and circuit breaker

for overcurrent protection should be provided in the

exclusive line.

(3) To prevent possible hazards from insulation failure, the

unit must be grounded.

(4) Each wiring connection must be done in accordance

with the wiring system diagram. Wrong wiring may

cause the unit to misoperate or become damaged.

(5) Do not allow wiring to touch the refrigerant tubing,

compressor, or any moving parts of the fan.

(6) Unauthorized changes in the internal wiring can be very

dangerous. The manufacturer will accept no

responsibility for any damage or misoperation that

occurs as a result of such unauthorized changes.

(7) Regulations on wire diameters differ from locality to

locality. For field wiring rules, please refer to your

LOCAL ELECTRICAL CODES before beginning.

You must ensure that installation complies with all

relevant rules and regulations.

(8) To prevent malfunction of the air conditioner caused by

electrical noise, care must be taken when wiring as

follows:

● The remote control wiring and the inter-unit control wiring

should be wired apart from the inter-unit power wiring.

● Use shielded wires for inter-unit control wiring between

units and ground the shield on both sides.

(9) If the power supply cord of this appliance is damaged, it

must be replaced by a repair shop appointed by the

manufacturer, because special purpose tools are

required.

5-2. Recommended Wire Length and Wire Diameter for Power Supply System

Outdoor unit

(A) Power supply

Wire size

Max. length

CHDX09053

64 ft.

60 A

AWG #8

CHDX14053

100 ft.

80 A

AWG #4

Time delay fuse or

circuit capacity

Indoor unit

Time delay fuse or

circuit capacity

(B) Power supply

AWG #14

K

A, X, T, U

Type

Type

15 A

15 A

15 A

D

Max. 492 ft.

Max. 426 ft.

Max. 196 ft.

NOTE

* With ring-type wire terminal.