How to install the outdoor unit – Sanyo R410A User Manual

Page 55

Advertising
background image

(Positions where anchor bolts are fastened)

31-7/64 (Installation hole pitch)

3

7-1

3

/3

2 (Maxim

u

m dime

ns

io

ns

)

35-3/64 (Ceiling panel dimensions)

3

6-7/

3

2 (I

ns

tallatio

n

hole pitch)

3

5-

3

/64 (Ceili

ng

pa

n

el dime

ns

io

ns

)

Installation anchor hole (4 – 19/32

× 25/32 oval holes)

4. HOW TO INSTALL THE OUTDOOR UNIT

4-1. Transporting

When transporting the unit, have it delivered as close to the installation site as

possible without unpacking. Use a hook for suspending the unit. (Fig. 4-1)

● When hoisting the outdoor unit, pass ropes or straps under the bottom plate

as shown in the figure at right. When hoisting, the angle between the rope

and top panel must be 70° or greater so that the rope does not come into

contact with the fan guard.

(Use 2 lengths of rope 25 ft. long or longer.)

● When passing the ropes through the square holes of the bottom plate:

Place the rope in the outer edge of the square holes.

● Use protective panels or padding at all locations where the rope contacts the

outer casing or other parts to prevent scratching. In particular, use protective

material (such as cloth or cardboard) to prevent the edges of the top panel

from being scratched.

● Be careful of the fan.

There is danger of injury if the fan starts to turn during inspection. Be sure to

turn OFF the remote power switch before beginning inspection.

4-2. Installing the Outdoor Unit

(1) Use anchor bolts (M12 or 15/32") or similar to securely anchor the unit in

place. (Fig. 4-2)

(2) Be sure the rubber vibration insulator and platform extend to the inside of the

legs. In addition, the washers used to anchor the unit from the top must be

larger than the installation anchor holes. (Figs. 4-2 and 4-3)

Fig. 4-1

Fig. 4-2

Fig. 4-3

(3

-15/16)

(3-15/16)

3

-29/64

25/

3

2

1-31/32

Washer

Plate leg

Base

Anchor bolts

Vibration insulator

CAUTION

1-33/64

19/

3

2

1-

3

1/

3

2

4 – 19/32 25/32 hole

(Detailed view of legs)

Su

rf

ace where

ins

tallatio

n

a

n

chor

br

ac

k

e

ts

are

ins

talled

Unit: in.

Unit: in.

74-1/64 (Ceiling panel dimensions)

70-5/64 (Installation hole pitch)

35-3/64 (Ceiling panel dimensions)

35-3/64 (Ceiling panel dimensions)

35-

3/64 (Ceili

ng

pa

nel dime

ns

io

ns

)

31-7/64 (Installation hole pitch)

31-7/64 (Installation hole pitch)

3

6-7/

3

2 (I

ns

tallatio

n

hole pitch)

3

7-1

3

/3

2 (Maxim

u

m dime

ns

io

ns

)

The vibration insulator, base, or platform must
be large enough to bear the full surface of the
base plate legs.

Unit: in.

Top view

55

Fig. 4-4

07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 55