Sanyo R410A User Manual

Page 71

Advertising
background image

YES

Make necessary corrections.

Check the alarm

contents.

Check the alarm contents.

Turn OFF the indoor and

outdoor unit power.

NO

YES

NO

*1

*2

*3

*3

*2

CASE 1

CASE 2

CASE 3B

CASE 3A

YES

YES

NO

YES

NO

NO

NO

YES

YES

NO

Recheck the items to check before the test run.

Have the outdoor sub units been connected?

Are the inter-unit control wires

connected to more than 1 refrigerant

system?

Is it possible to turn ON the power only

for the 1 refrigerant system where the

test run will be performed?

Will automatic address setting be

performed in Heating mode?

Is it OK to start the compressors?

Turn ON the indoor and

outdoor unit power.

Short-circuit the mode change pin

(CN101) on the outdoor main unit PCB.

At the same time, short-circuit the

automatic address pin (CN100) for 1

second or longer, then release it.

Short-circuit the automatic address

pin (CN100) on the outdoor main

unit PCB for 1 second or longer,

then release it.

Short-circuit the automatic address pin (CN100)

on the outdoor main unit PCB for 1 second or

longer, then release it.

Start indoor and outdoor unit

cooling operation.

LED 1 and 2 blink alternately.

Start indoor and outdoor unit

heating operation.

LED 1 and 2 blink alternately.

LED 1 and 2 blink alternately

(about 2 or 3 minutes).

Is it OK to start the compressors?

Turn ON the indoor and

outdoor unit power.

Turn OFF the indoor and

outdoor unit power.

Turn ON the indoor and

outdoor unit power for that

refrigerant system only.

Are LEDs 1 and 2 on the

outdoor unit PCB OFF?

Are LEDs 1 and 2 on the

outdoor unit PCB OFF?

Set the unit address.

Set the No. of outdoor units.

Set the No. of indoor units.

Set the system address.

When multiple outdoor main units exist, disconnect the terminals

extended from the shorted plugs (CN003) at all outdoor main unit

PCBs except for 1.

Alternatively, move the sockets to the OPEN side.

<Outdoor unit control PCB>

Unit No. setting switch

(S007)

<Outdoor unit control PCB>

Unit No. setting switch

(S006)

<Outdoor unit control PCB>

Unit No. setting switch

(S004 and S005)

<Outdoor unit control PCB>

Unit No. setting switch

(S002 and S003)

(Check the link wiring.)

*1

The unit with the unit

No. set to 1 is the
main unit. All other
units are sub units.

Note: It is not necessary to remove the socket

that is used to short-circuit the terminal
plugs from the outdoor sub unit PCBs.

Refer to “Table of
Self-Diagnostic Functions and
Description of Alarm Displays.”

*2 A minimum of 5 hours must have passed after the

power was turned ON to the outdoor unit.

*3 All indoor units operate in all refrigerant systems

where the power is ON.

Check that test run preparation is OK.

(Do not allow the short-circuited pins to remain short-circuited.)

Refer to the remote

controller test-run

settings.

Set the wired remote controller for test run.

Does system operate?

Return remote control to normal mode

Check and make corrections according to

“Table of Self-Diagnostic Functions.”

End test run.

Make necessary

corrections

Refer to Fig. 8-4

Items to Check Before the Test Run

1. Turn the remote power switch on at least 5 hours

before the test, in order to energize the crank
case heater.

2. After performing the leak inspection, applying

vacuum, and performing refrigerant charge for
the tubing which is connected on-site, fully open
the outdoor unit service valve. However if only
one outdoor unit is installed, a balance tube is
not used. Therefore, leave the valve fully closed.

3. When replacing the control PCB, be sure that

the settings on the new PCB match those on the
old PCB.

4. Use caution when making the settings. If there

are duplicated system addresses, or if the
settings for the Nos. of the indoor units are not
consistent, an alarm will occur and the system
will not start.

5. These settings are not made on the indoor unit

PCB.

8-2. Test Run Procedure

Fig. 8-3

71

07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 71

Advertising