Checking of limit density

Density limit is determined on the basis of the size of a room

using an indoor unit of minimum capacity. For instance, when

an indoor unit is used in a room (floor area 161 ft.

2

× ceiling

height 8.8 ft. = room volume 1417 ft.

3

), the graph at right

shows that the minimum room volume should be 2455 ft.

3

(floor area 279 ft.

2

) for refrigerant of 418 oz.

<Determination by calculation>

Overall refrigerant charge amount for the air conditioner: oz

(Minimum room volume for indoor unit: ft.

3

)

=

418 (oz)

= 0.29 (oz/ft.

3

) < 0.3 (oz/ft.

3

)

1417 (ft.

3

)

Therefore, openings such as louvers are not required for this

room.

0

0

57

114

170

227

284

341

398

454

0

500

1000

1500

2000

2500

3000

3500

4000

400

200

600

800 1000 1200

Total amount of refrigerant

Mi

n

. i

n

door v

o

lu

me

Mi

n

. i

n

door floor area

(whe

n

the ceili

ng

i

s

8

.8

ft.

hi

g

h)

ft.

3

ft.

2

oz

Range above
the density limit of
0.3 oz/ft.

3

(countermeasures
needed)

Range below
the density limit of
0.3 oz/ft.

3

(countermeasures
not needed)

● Obtain liquid tubing size from Tables 1-9, 10, 11, 12 and 15.

Main tubing

LA = ø5/8 (ft.) (Total capacity of indoor unit is 179,400 BTU/h)

The longest tubing length in this example

LB = ø1/2 (ft.) (Total capacity of indoor unit is 131,600 BTU/h)

(LA = 131 ft.)

LC = ø3/8 (ft.) (Total capacity of indoor unit is 83,800 BTU/h)

Distribution joint tubing

Outdoor side

A: ø3/8 (ft.)

B: ø3/8 (ft.)

(from outdoor unit connection tubing)

Indoor side

1: ø3/8 (ft.)

2: ø3/8 (ft.)

3: ø3/8 (ft.)

4: ø3/8 (ft.) (from indoor unit connection tubing)

● Obtain charge amount for each tubing size

Note that the charge amounts per 1 meter are different for each liquid tubing size.

ø5/8 (ft.)

→ LA

: 131 ft.

× 1.99 oz/ft. = 261 oz

ø1/2 (ft.)

→ LB

: 16 ft.

× 1.38 oz/ft.

=

22 oz

ø3/8 (ft.)

→ LC + A – B + 1 – 4

: 225 ft.

× 0.602 oz/ft. = 135 oz

Total 418 oz

Additional refrigerant charge amount is 418 oz.

Be sure to check the limit density for

the room in which the indoor unit is

installed.

CAUTION