Using the Modbus Ports

870 USE 101 10 V.2

123

Four-Wire Cabling Schemes for Modbus RS485 Networks

Introduction

Four-wire cabling schemes may be used for single master/slave communications.
Only one master is allowed. The master may be located anywhere in the network.

Length

The maximum length of cable from one end of network to other is 2000 ft. (609 m).

Number of
Devices

The maximum number of devices in a network is 64 if all are Momentum devices.
Otherwise, the maximum is 32.

Termination

You must terminate both ends of the cable run with special terminating resistors.

Master Cable

The master of this master/slave cabling scheme must be connected on at least one
side to a master cable, a special cable that crosses the transmit and receive lines.

The other side may be connected to a master cable, or, if the master is at one end
of the cable run, a terminating resistor.

Continued on next page

Description

Part Number

Modbus Plus or Modbus RS485 Terminating RJ45 Resistor Plugs
(pack of 2).
Color code - red

170 XTS 021 00

Description

Part Number

Modbus RS485 (RJ45/RJ45) Master Communication Cable

170 MCI 041 10

Modbus Plus or Modbus RS485 Terminating RJ45 Resistor Plugs
(pack of 2).
Color code - blue

170 XTS 021 00