Configuring a Modbus Plus Network in Concept with Peer Cop

870 USE 101 10 V.2

373

Adjusting the Amount of Extension Memory

Introduction

The default amount of memory allotted for Configuration Extension is 100 words.
This amount may be adjusted within the Peer Cop dialog box.

Extension
Memory Size

The minimum Peer Cop memory requirement is 20 words; the maximum is 4041
words.

Estimating How
Much Memory to
Reserve

Follow these guidelines for estimating the amount of extension memory you will
need for your Peer Cop database:

Changing the
Amount of
Memory

Type the desired size in the Expansion Size

text box or use your mouse to adjust

the button on the horizontal slider.

For...

Add...

Up to a maximum of...

Overhead

9 words

--

Global output

5 words

--

Global input

number of words=
number of devices x
(1 + 2 x number of device subentries)

1088 words

Specific output

2 words for every device entry in Peer Cop

128 words

Specific input

2 words for every device entry in Peer Cop

128 words