Configuring a Modbus Plus Network in Concept with Peer Cop

392

870 USE 101 10 V.2

Specifying References for Input and Output Data, Continued

Defining the
Global Inputs,
Continued

Next Step

Defining the references for the next node.

Step

Action

3

Type the value 1 in the Index column, indicating that the CPU will receive part of
the global input data beginning with the first word.

4

Type the value 5 in the Length column, indicating that the CPU will accept five
words of the global input data. Leave the default

BIN

setting.

5

Click <OK>.