Other Default Settings in the Peer Cop Dialog Box

Overview

This section describes the default settings for Health Timeout and Last Value.

Diagram

The first time you access the Peer Cop dialog box, the following screen appears:

Health Timeout

The default Timeout is

500 ms.

Timeout is the maximum interval that Modbus Plus on a Peer-Copped device will
remain healthy without communication activity. If this interval is exceeded, the
device will clear its network health bit and will no longer try to communicate via
Modbus Plus.

The timeout interval must be in the range 20...2000 ms, and it must be specified as
an increment of 20 ms.