Specifying references for output data – Schneider Electric Processor Adapter User Manual

Page 384

Advertising
background image

Configuring a Modbus Plus Network in Concept with Peer Cop

384

870 USE 101 10 V.2

Specifying References for Output Data

Introduction

This section describes how to specify the references for output data. In this
example, you will start by accessing the device at Modbus Plus address 3, which is
a 170 AD0 340 00 16-point output module.

Device
Requirements

When you use Peer Cop to handle a Modbus Plus I/O architecture, you need to
know which type of I/O you are configuring at each network address and how many
input or output references each device requires. In this example, we will create a
specific output reference with a length of one word (16 bits).

We also will assign a 4

x register (400016) as a specific input to the CPU. When the

the 170 ADO 340 00 sends input data to the CPU, it will be sent to this register.

Procedure

Follow the steps in the table below to define the specific output.

Continued on next page

Step

Action

1

Click on the Specific Output... button in the Peer Cop dialog box.

Result: The Specific Output dialog box appears.

Advertising