Configuring a Modbus Plus Network in Concept with Peer Cop

394

870 USE 101 10 V.2

Defining the References for the Next Node, Continued

Defining Specific
Outputs

Follow the steps in the table below to define the specific output in Peer Cop.

Continued on next page

Step

Action

1

Click on the Specific Output... button.

Result: The Specific Output dialog box appears.

2

Since you are addressing the device at address 1, you will use the line for Source
1. Type the value 400024

on that line in the Dest. Ref. column.

3

Type the value 16 in the Length column, indicating that 16 words of data will be
exchanged. In this case, we will leave the default BIN setting.

4

Click <OK>.