Maintenance – Lochinvar TISUN SCH-I-O User Manual

Page 42

Advertising
background image

42

7

Maintenance

ƽ WARNING

Follow the service and maintenance
procedures given throughout this manual
and in component literature shipped
with the solar components. Failure to
perform the service and maintenance
could result in damage to the solar
system. Failure to follow directions in the
manual and component literature could
result in severe personal injury, death or
substantial property damage.

ƽ WARNING

The solar heating system should be
inspected annually only by a qualified
service technician. In addition, the
maintenance and care of the solar
collection system explained in the
following pages must be performed
to assure maximum system efficiency
and reliability. Failure to service and
maintain the solar system could result in
equipment failure.

ƽ WARNING

Turn off power to electrical components
before any service operation on the solar
system except as noted otherwise in this
instruction manual. Failure to turn off
electrical power could result in electrical
shock, causing severe personal injury or
death.

These maintenance items must be performed annually to
ensure proper operation of the solar collection system.

Address reported problems

1. Inspect any problems reported by the owner and correct
before

proceeding.

Fluid installation

Follow these installation procedures:

1. Clean new or lightly corroded existing systems with a 1% or

2% solution of trisodium phosphate in water prior to the

installation of industrially inhibited propylene glycol fluid.

2. Extensively corroded existing systems should be cleaned by

an industrial cleaning company and all corroded

components should be replace.

3. Use only quality water in solution with the propylene

glycol fluid. Use water with low levels (less than 25 ppm) of

chloride and sulfate, and less than 50 ppm of hard water

ions (Ca++, Mg++). Distilled or deionized water is

recommended.

System design considerations

Avoid use of automatic water make-up systems to prevent
undetected dilution of the propylene glycol and possible
contamination of the water system.

Technical data

Typical Properties of Dowfrost HD Fluid*

Composition (% by weight)
Propylene

Glycol

94

Performance Additives

6

Color

Fluorescent

Yellow

Specific Gravity
15/15°C (60/60°F)

1.053 - 1.063

pH of Solution
(50%

glycol)

9.5

-

10.5

Reserve Alkalinity (min.)

15.0 ml

*Typical properties, not to be construed as specifications.
Complete sales specifications are available on request.

SCH Collectors Installation & Operation Manual

Freezing and boiling points of Aqueous Solutions

Freezing

Temperature, °F

% Glycol

by Volume

Boiling

Temperature, °F

26

10

212

19

20

213

8

30

216

-7

40

219

-28

50

222

Advertising