UPS OPERATING INSTRUCTIONS

EATON Powerware

®

9395 UPS (650–825 kVA) Installation and Operation Manual

S 164201725 Rev 2 www.powerware.com

7−6

7.2.6

Display Menu Operation

Table 7-3 describes the menu functions and and how to use them.

Table 7-3. Display Menu Operation

Function

Subfunction

Operation

Events

Press the EVENTS pushbutton on the main menu bar or History menu bar to display a listing of
all system events that are currently active. The most recent event is listed first. As events clear,
they are removed from the Active System Events listing. To scroll through the events, press the
up or down arrow pushbutton on the menu bar.

User History

Press the HISTORY pushbutton on the Active Events menu bar to display the User History Log.
The User History Log lists up to 2048 events in chronological order, with the most recent event
listed last (once 2048 is reached, the earliest event is overwritten). The end of the log (the most
recent events) is displayed first; scroll upward to view older event listings. To scroll through the
events, press the up or down arrow pushbutton on the menu bar. To return to the Active Events
screen, press the EVENTS pushbutton on the menu bar.

Service History

The Service History Log is for service personnel and is password protected. If the customer
needs access to the log, contact an Eaton service representative.
Press the SERVICE pushbutton on the User History menu bar to display the Service History Log.
The Service History Log lists up to 2048 events in chronological order, with the most recent event
listed last (once 2048 is reached, the earliest event is overwritten). The end of the log (the most
recent events) is displayed first; scroll upward to view older event listings. To scroll through the
events, press the up or down arrow pushbutton on the menu bar. To return to the User History
screen, press the USER pushbutton on the menu bar. To return to the Active Events screen,
press the EVENTS pushbutton on the menu bar.

Meters–UPS
Meters–UPM

The Meter screens show the UPS meter readings for the unit. The default voltage displayed on
these screens is phase−to−neutral. However, an authorized Eaton Customer Service Engineer
can change the screens to display the voltage phase−to−phase (A−B, B−C, C−A). Press the
METERS pushbutton on the main menu bar to display the Meter screens. To scroll through the
meter screens, press the up or down arrow pushbutton on the menu bar. The current UPS
readings are displayed in the information area of the screen.

Output–UPS
Output–UPM 1, 2, 3, 4

The Output screen shows output voltage (phase-to-neutral), output current (each phase), and
frequency being supplied by the UPS, as well as the kVA, kW, and power factor measurements.

Input–UPS
Input–UPM

The Input screen shows input voltage (phase-to-neutral), input current (each phase), and
frequency of the incoming utility source, as well as the kVA, kW, and power factor
measurements.

Bypass

The Bypass screen shows the bypass input voltage (phase-to-neutral), input current (each
phase), and frequency of the incoming utility source, as well as the kVA, kW, and power factor
measurements.

Battery–UPS
Battery–UPM

The Battery screen displays the battery voltage (Vdc), the battery current (Idc), the minutes of
battery time remaining, and battery temperature. Battery temperature must be set up by an
authorized Eaton Customer Service Engineer. When battery life decreases to less than 20%,
Check Battery is displayed.

Statistics

The Statistics screen displays the hours on line and the total kW hours used.

Output Current–UPS
Output Current–UPM

The Output Current screen displays a real-time bar graph of the output current of the UPS. The
graph shows the current for each phase.

Output Power – UPM

The Output Power screen displays the power in kW and kVA for each UPM.

System Level 0 Setup

Function Selection

This screen can be used to set the screen contrast, show the firmware versions installed,
identify the unit type and enter a password to access Level 1 functions. Press the SETUP
pushbutton on the main menu bar to display the System Setup Level 0 Screen. No password is
necessary to access Level 0 functions. Use the up or down arrow pushbutton to highlight the
setup function screen desired, then press the SELECT pushbutton to display the function screen.