UPS OPERATING INSTRUCTIONS

EATON Powerware

®

9395 UPS (650–825 kVA) Installation and Operation Manual

S 164201725 Rev 2 www.powerware.com

7−19

C

A

U

T

I

O

N

Do not attempt to restart the system after the REPO until the cause of the shutdown has been identified and
cleared.

2.

To deactivate the REPO switch in preparation for restarting the UPS, insert the
supplied key and rotate clockwise until the red pushbutton releases (see
Figure 7-7). To remove the key, rotate the key back to the vertical position.

3.

Restart the UPS by following the procedure in paragraph 7.3.1 on page 7−11 or
7.3.2 on page 7−12.

W

A

R

N

I

N

G

Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.

Deactivated

Unlock pushbutton to release

Activated

Pushbutton locked into place

Figure 7-7. REPO Operation