UPS SYSTEM INSTALLATION

EATON Powerware

®

9395 UPS (650–825 kVA) Installation and Operation Manual

S 164201725 Rev 2 www.powerware.com

4−28

4.8.2

Battery Power Wiring

C

A

U

T

I

O

N

When sizing the battery system, do not exceed the internal battery charger capabilities. See Chapter 10,

Product Specifications," for maximum battery charger currents.

To install wiring to connections:

NOTE An installed FI−UPM is always designated as UPM 4.

1.

Route the battery cables between the ISBM section and the battery system or
battery disconnect. See Figure 4-18, Figure 4-20, Figure 4-25, and Figure 4-26 for
wiring access information and terminal locations.

2.

If wiring the UPS for a common battery, proceed to Step 3; if wiring for a
separate battery, proceed to Step 5.

3.

Using hardware from the external wiring terminal hardware kit (see Table 3-10 on
page 3−14), connect the positive, negative, and ground DC power wiring from the
battery system or disconnect to the ISBM section battery and ground terminals.
Use both sets of terminals shown in Figure 4-25 as needed. See paragraph 3.2.2
on page 3−8 for wiring and termination requirements.

4.

Proceed to Step 6.

5.

Using hardware from the external wiring terminal hardware kit (see Table 3-10 on
page 3−14), connect the positive, negative, and ground DC power wiring from the
battery systems or disconnects to the ISBM section battery and ground
terminals. Use one set of terminals for each UPM as shown in Figure 4-26. See
paragraph 3.2.2 on page 3−8 for wiring and termination requirements.

6.

After wiring the UPS system to the facility power and critical load, be sure to
ground the system according to local and/or national electrical wiring codes.

7.

If wiring interface connections, proceed to paragraph 4.9; otherwise, proceed to
Step 8.

8.

When all wiring is complete, reinstall the top and bottom safety shield panels
removed in paragraph 4.8.1, Step 2 on page 4−18. Secure with the retained
hardware.

9.

Reinstall the left front panel removed in paragraph 4.8.1, Step 1 on page 4−18 and
secure with the retained hardware.