Chapter 10 product specifications, 1 model numbers, 2 specifications – Powerware 9395 UPS and Plus 1 UPS 650825 kVA User Manual

Page 187: 1 ups input

Advertising
background image

EATON Powerware

®

9395 UPS (650–825 kVA) Installation and Operation Manual

S 164201725 Rev 2 www.powerware.com

10−1

Chapter 10

Product Specifications

10.1

Model Numbers

The UPS is housed in a free-standing cabinet, divided into two sections with safety
shields behind the door and front panels. The UPS is available in 50 or 60 Hz with
various output power ratings.

Models

Power Rating

Frequency

Powerware 9395−825/650

650 kVA

50/60 Hz

Powerware 9395−825/750

750 kVA

50/60 Hz

Powerware 9395−825/825

825 kVA

50/60 Hz

The following sections detail the input, output, environmental, and battery
specifications for the UPS.

10.2

Specifications

10.2.1

UPS Input

Operating Input Voltage

400 Vac
480 Vac

Operating Input Frequency Range

50/60 Hz

Operating Input Current

See Table 3-4 on page 3−9, Table 3-5 on page 3−10, or Table 3-6 on
page 3−11
.

Reduced for Generator
Adjustable

Input Current Harmonic Content

5% THD at full load

Power Factor

Minimum 0.99

Line Surges

6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4

Battery Voltage

480 Vdc

Battery Charging Capacity

Configurable per UPM at nominal line voltage:
Up to 120A with less than 85% load
Up to 80A with 100% load

Battery Shunt Trip

48 Vdc

Figure 10Table 10