UPS INSTALLATION PLAN AND UNPACKING

EATON Powerware

®

9395 UPS (650–825 kVA) Installation and Operation Manual

S 164201725 Rev 2 www.powerware.com

3−2

Table 3-1. UPS Cabinet Weights

Model

Section

Weight

kg (lb)

Shipping

Installed

Powerware 9395−825/650

ISBM

1498 (3302)

1390 (3064)

UPM

1590 (3505)

1482 (3267)

Powerware 9395−825/750

ISBM

1498 (3302)

1390 (3064)

UPM

1590 (3505)

1482 (3267)

Powerware 9395−825/825

ISBM

1498 (3302)

1390 (3064)

UPM

1590 (3505)

1482 (3267)

The UPS cabinet uses forced air cooling to regulate internal component temperature.
Air inlets are in the front of the cabinet and outlets are in the top. Allow clearance in
front of and above each cabinet for proper air circulation. The clearances required
around the UPS cabinet are shown in Table 3-2.

Table 3-2. UPS Cabinet Clearances

From Top of Cabinet

457.2 mm (18") minimum clearance for ventilation

From Front of Cabinet

914.4 mm (36") working space

From Back of Cabinet

None Required

From Right Side of Cabinet

152.4 mm (6") working space

From Left Side of Cabinet

None Required

The basic environmental requirements for operation of the UPS are:

S

Ambient Temperature Range:

0–40°C (32–104°F)

S

Recommended Operating Range: 20–25°C (68–77°F)

S

Maximum Relative Humidity:

95%, noncondensing

C

A

U

T

I

O

N

If battery systems are located in the same room as the UPS, the battery manufacturer’s environmental
requirements should be followed if they are more stringent than the UPS requirements. Operating
temperatures above the recommended range will result in decreased battery life and performance, and may
reduce or void the battery warranty.

The UPS ventilation requirements are shown in Table 3-3.

Table 3-3. Air Conditioning or Ventilation Requirements During Full Load Operation

Rating

Input/Output

Voltage

Heat Rejection

BTU/hr

 1000 (kg−cal/hr)

Ventilation Required for

Cooling Air Exhaust

650 kVA

400/400

125 (31613)

Approximately 2265 liter/sec (4800 cfm)

With Field Installed UPM:

Approximately 3020 liter/sec (6400 cfm)

480/480

127 (31933)

750 kVA

400/400

145 (36476)

480/480

146 (36845)

825 kVA

400/400

159 (40124)

480/480

161 (40530)