UPS INSTALLATION PLAN AND UNPACKING

EATON Powerware

®

9395 UPS (650–825 kVA) Installation and Operation Manual

S 164201725 Rev 2 www.powerware.com

3−9

For external wiring requirements, including the minimum AWG size of external wiring,
see Table 3-4 for installations using a common battery system, Table 3-5 for
installations using a separate battery system, or Table 3-6 for separate rectifier feed
installations. Wire sizes listed are for copper wiring only.

Table 3-4. Input/Output Ratings and External Wiring Requirements for the Powerware 9395−825/650, 9395−825/750, and 9395−825/825
– Common Battery

Basic Unit Rating

Units

Rating 50/60 Hz

kVA

kW

650
585

650
591

750
675

750
682

825

7742

825
750

Input and Output Voltage

Volts

400/400

480/480

400/400

480/480

400/400

480/480

AC Input to UPS Rectifier (0.98 Minimum pF)

Full load current plus battery recharge current
(3) Phases, (1) Ground

A

Amps

1079

891

1245

1028

1369

1130

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(4)

500

(3)

500

(4)

500

(4)

500

(5)

500

(4)

AC Input to UPS Bypass (Four Wire)

Full Load Current
(3) Phases, (1) Ground

B

Amps

938

782

1083

902

1191

992

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(3)

350

(3)

500

(4)

500

(3)

500

(4)

500

(4)

AC Input to UPS Bypass (Five Wire)

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

B

Amps

938

782

1083

902

1191

992

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

400

(4)

500

(3)

500

(5)

500

(4)

500

(5)

500

(5)

DC Input from Battery Disconnect to UPS

(1) Positive, (1) Negative

C

Total Amps

1280

1280

1502

1502

1600

1600

Minimum Conductor Size
Number per Pole

AWG or kcmil

(each)

350

(6)

350

(6)

500

(6)

500

(6)

500

(6)

500

(6)

AC Output to Critical Load (Four Wire)

Full Load Current
(3) Phases, (1) Ground

D

Amps

938

782

1083

902

1191

992

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(3)

350

(3)

500

(4)

500

(3)

500

(4)

500

(4)

AC Output to Critical Load (Five Wire)

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

D

Amps

938

782

1083

902

1191

992

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

400

(4)

500

(3)

500

(5)

500

(4)

500

(5)

500

(5)

Neutral Bonding Jumper (Four Wire Output Only)

Minimum Conductor Size
Number

AWG or kcmil

(each)

4/0

(1

4/0

(1)

4/0

(1

4/0

(1)

4/0

(1

4/0

(1)

NOTE Callout letters

A

,

B

,

C

, and

D

map to Figure 6-5, Figure 6-7, Figure 6-9, or Figure 6-11 starting on page 6−8.