7 system status screen and controls – Powerware 9395 UPS and Plus 1 UPS 650825 kVA User Manual

Page 150

Advertising
background image

UPS OPERATING INSTRUCTIONS

EATON Powerware

®

9395 UPS (650–825 kVA) Installation and Operation Manual

S 164201725 Rev 2 www.powerware.com

7−8

Table 7-3. Display Menu Operation (continued)

Operation

Subfunction

Function

Com Port Selection

The Com Port Setup screen allows selection of the serial COM port to set up. Select COM PORT
SETUP from the System Setup Level 1 menu to display the COM Port Setup screen. Use the up or
down arrow pushbutton to highlight the the COM port to be set up, then press the SELECT
pushbutton

.

To return to the System Setup screen, press the return arrow pushbutton

.

Com Port Setup

The COM Setup screen is used to change and save the settings for the selected serial
communication port. The COM port number selected from the COM Port Setup screen displays.
If the changes are not wanted, use the ABORT pushbutton to return to the COM Port Setup
screen. Use the up or down arrow pushbutton to highlight the setting to be changed. Use the
return arrow pushbutton to toggle through the values for the setting to make the change. Press
SAVE or ABORT. Once the action is completed, the COM Port Setup screen is displayed.

Control

See paragraph 7.2.7 for details.

7.2.7

System Status Screen and Controls

Press the

CONTROLS

pushbutton on the main menu bar to display the System Status

screen. Normal operation, transfer to bypass, charger control, UPM startup and
shutdown and LOAD OFF commands are controlled through this screen. In addition,
the screen displays the current status of the UPS and indicates whether the UPS is in
Maintenance Bypass or Bypass, and the state of the UPM and battery charger.
Figure 7-5 shows the System Status screen.

Use the or pushbutton on the System Status menu bar to highlight the
command screen desired, then press the

CONTROLS

pushbutton to display the

command menu screen.

Table 7-4 lists the typical System Status Screen Messages that are displayed during
UPS operation.

Table 7-5 describes the control functions and provides instructions to access and use
the command menu screens.

For detailed information about using the System Controls, see paragraph 7.3.

MAINTENANCE BYPASS

BYPASS

UPM: OFFLINE

SHUTDOWN

:

AVAILABLE

:

OFF

:

SYSTEM STATUS

CONTROLS

ESC

CHARGER

OFF

:

UPS

Figure 7-5. Typical System Status Screen

Advertising