3 inspecting and unpacking the ups cabinets – Powerware 9395 UPS and Plus 1 UPS 650825 kVA User Manual

Page 43

Advertising
background image

UPS INSTALLATION PLAN AND UNPACKING

EATON Powerware

®

9395 UPS (650–825 kVA) Installation and Operation Manual

S 164201725 Rev 2 www.powerware.com

3−21

3.3

Inspecting and Unpacking the UPS Cabinets

The UPS cabinet is divided into two sections palleted separately for shipping. The
sections are shipped bolted to wooden pallets (see Figure 3-11 and Figure 3-12) and
protected with outer protective packaging material.

W

A

R

N

I

N

G

The UPS sections are heavy (see Table 3-1 on page 3−2). If unpacking and unloading instructions are not
closely followed, the cabinets may tip and cause serious injury.

C

A

U

T

I

O

N

To prevent damage to the wiring channel and wiring in the UPM section base when lifting or moving the
cabinet:

S

Lift and move the UPM section using only the front or rear forklift slots.

S

Verify that the forklift forks are in a horizontal position before inserting them into the forklift slots.
DO NOT angle fork tips upward.

S

Insert the forks all the way through the base. DO NOT insert forks partially into the base to move the
cabinet.

S

Forks may be partially inserted into the front or rear forklift slots for minor positioning if the forks are
kept in a horizontal position with no upward angling.

S

DO NOT use the forklift slots on the end of the cabinet to move the cabinet.

S

End forklift slots may be used for minor positioning if the forks are kept in a horizontal position with no
upward angling.

If these instructions are not followed, damage to the wiring channel and wiring will occur.

1.

Carefully inspect the outer packaging for evidence of damage during transit.

C

A

U

T

I

O

N

Do not install a damaged cabinet. Report any damage to the carrier and contact an Eaton service
representative immediately.

NOTE For the following step, verify that the forklift or pallet jack is rated to handle the weight of the
cabinet (see Table 3-1 on page 3−2 for cabinet weight).

2.

Use a forklift or pallet jack to move the packaged cabinets to the installation site,
or as close as possible, before unpacking. If possible, move the cabinets using
the pallet. Insert the forklift or pallet jack forks from the right side of the pallet
(facing the cabinet), between the supports on the bottom of the pallet (see
Figure 3-8 and Figure 3-9 on page 3−6 for the UPS cabinet center of gravity
measurements). If the cabinets must be moved using the cabinet front or rear
fork lift slots, see the caution statement at the beginning of this procedure.

C

A

U

T

I

O

N

Do not tilt the UPS cabinets more than 10° from vertical or the cabinets may tip over.

3.

Set the pallet on a firm, level surface, allowing a minimum clearance of 3m (10 ft)
on each side for removing the cabinet from the pallet.

NOTE The ISBM and UPM sections are shipped with debris shields covering the ventilation grills on top of
the sections (see Figure 4-17 on page 4−19). Do not remove the debris shields until installation is complete.

Advertising