UPS INSTALLATION PLAN AND UNPACKING

EATON Powerware

®

9395 UPS (650–825 kVA) Installation and Operation Manual

S 164201725 Rev 2 www.powerware.com

3−14

Table 3-10. Supplied External Wiring Terminal Hardware Kit

Part

Size

Quantity

Terminals Used On

Eaton Part Number

Bolt, Grade 5

M10 x 25 mm

15

Ground

180190078−087

Bolt, Grade 5

M12 x 45 mm

92

Rectifier Input, Bypass Input, Battery Input,

Output, and Neutral

180190078−113

Flat Washer

M10

15

Ground

180500036−100

Flat Washer

M12

184

Rectifier Input, Bypass Input, Battery Input,

Output, and Neutral

180500036−120

Conical Washer

M10

15

Ground

180500037−100

Conical Washer

M12

92

Rectifier Input, Bypass Input, Battery Input,

Output, and Neutral

180500037−120

Nut

M12

92

Rectifier Input, Bypass Input, Battery Input,

Output, and Neutral

180200001−07

Table 3-11. Recommended Installation Parts and Tools (Not Supplied by Eaton

)

Part

Size

Quantity

Manufacturer

Part Number

Notes

Long Barrel 2-Hole Lug

2/0 AWG

As required

Thomas & Betts

54862BE

Copper wire only

3/0 AWG

Thomas & Betts

54864BE

4/0 AWG

Thomas & Betts

54866BE

250 MCM

Thomas & Betts

54868BE

300 MCM

Thomas & Betts

54870BE

350 MCM

Thomas & Betts

54872BE

400 MCM

Thomas & Betts

54874BE

500 MCM

Thomas & Betts

54876BE

Manual Hydraulic Crimp Tool

14 Ton

1

Thomas & Betts

TBM14M

Die Set

N/A

1

Thomas & Betts

15506

Table 3-12. Separate Rectifier Input UPM Power Cable Terminations for the Powerware 9395−825/650, 9395−825/750, and 9395−825/825

Terminal Function

Terminal

Function

Size of Pressure Termination

Tightening Torque

Nm (lb ft)

Type Screw

AC Input to each UPM Rectifier

E1

Phase A

2 − #6−250 kcmil

42.4 (375)

5/16" Hex

E2

Phase B

2 − #6−250 kcmil

42.4 (375)

5/16" Hex

E3

Phase C

2 − #6−250 kcmil

42.4 (375)

5/16" Hex