7.4.10

Using the UPS LOAD OFF Pushbutton or Command

A UPS Load Off is initiated by the

LOAD OFF

pushbutton from the main menu bar, the

Load Off command on the UPS Control Command screen, or Load Off command on
the Bypass Control Command screen. The UPS

LOAD OFF

controls the UPSs outputs

by powering down the UPS and de-energizing the critical load.

The UPSs (including Bypass) remain off until restarted.

NOTE The UPS Load Off controls each UPS independently and does not shutdown the whole distributed
bypass system. To immediately shutdown the whole system, use the REPO switch (see paragraph 7.4.11).

To use the

LOAD OFF

pushbutton:

1.

Press the

LOAD OFF

pushbutton on the UPS to shutdown.

The Load Off screen is displayed, providing a choice to proceed or abort the
shutdown.

C

A

U

T

I

O

N

All power to the critical load is lost when the LOAD OFF is selected in the following step. You should use this
feature only when you want to de-energize the critical load.

2.

To shut down the UPS, press

LOAD OFF

from the Load Off menu bar, and hold for

three seconds. To abort the shutdown, press

CANCEL

.

When LOAD OFF is selected and held for three seconds, the input, output,
battery, and bypass backfeed contactors open, and the power module is turned
off on the UPSs.

3.

If another UPS is to be shutdown, proceed to that UPS and repeat Steps 1 and 2.

C

A

U

T

I

O

N

Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and
cleared.

4.

Restart the UPS after pressing the

LOAD OFF

pushbutton by following the

procedure in paragraph 7.4.1 on page 7−20 or 7.4.2 on page 7−21.

W

A

R

N

I

N

G

Power is present inside the UPS cabinet sections until the upstream input feeder circuit breaker is opened.

To use the

LOAD OFF

command:

1.

Press the

CONTROLS

pushbutton on the main menu bar of the UPS to be

shutdown. The System Status screen is displayed.

2.

On the System Status screen, select either the

UPS

or the

BYPASS

command.

3.

Press the

CONTROLS

pushbutton on the System Status menu bar. The UPS or

Bypass Control Command screen is displayed.

4.

On the Control Command screen, select

LOAD OFF

.

5.

Press the

SELECT

pushbutton on the Command menu bar.

The Load Off screen is displayed, providing a choice to proceed or abort the
shutdown.