UPS INSTALLATION PLAN AND UNPACKING

EATON Powerware

®

9395 UPS (650–825 kVA) Installation and Operation Manual

S 164201725 Rev 2 www.powerware.com

3−13

For an UPS with common rectifier input terminals, E1 through E12 are 2-hole bus bar
mountings for standard NEMA 2-hole barrel lugs. The power wiring connections for
this equipment are rated at 90°C. See Table 3-9 for external power cable terminations,
Table 3-10 for supplied external wiring terminal hardware, and Table 3-11 for
recommended installation parts and tools not supplied by Eaton Corporation.

For an UPS with separate rectifier input terminals for the UPMs, E1 through E3 are
pressure terminations, UL and CSA rated at 90°C. See Table 3-12 on page 3−14 for
these power cable terminations.

Figure 4-20 through Figure 4-26 starting on page 4−24 show the location of the power
cable terminals inside the UPS.

Table 3-9. UPS External Power Cable Terminations for the Powerware 9395−825/650, 9395−825/750, and 9395−825/825

Terminal Function

Terminal

Function

Bus Landings

(using both sides of bus)

Tightening Torque

Nm (lb ft)

Bolt Size

AC Input to UPS Rectifier

E1

Phase A

4 – 2 bolt mounting

76 (56)

M12

E2

Phase B

4 – 2 bolt mounting

76 (56)

M12

E3

Phase C

4 – 2 bolt mounting

76 (56)

M12

AC Input to Bypass

E6

Phase A

6 – 2 bolt mounting

76 (56)

M12

E7

Phase B

6 – 2 bolt mounting

76 (56)

M12

E8

Phase C

6 – 2 bolt mounting

76 (56)

M12

AC Output to Critical Load

E9

Phase A

6 – 2 bolt mounting

76 (56)

M12

E10

Phase B

6 – 2 bolt mounting

76 (56)

M12

E11

Phase C

6 – 2 bolt mounting

76 (56)

M12

DC Input from Battery or Battery
Disconnect to UPS – Common
Battery

E4

Battery (+)

12 – 2 bolt mounting

76 (56)

M12

E5

Battery (−)

12 – 2 bolt mounting

76 (56)

M12

DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 1)

E4

Battery (+)

4 – 2 bolt mounting

76 (56)

M12

E5

Battery (−)

4 – 2 bolt mounting

76 (56)

M12

DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 2)

E4

Battery (+)

4 – 2 bolt mounting

76 (56)

M12

E5

Battery (−)

4 – 2 bolt mounting

76 (56)

M12

DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 3)

E4

Battery (+)

4 – 2 bolt mounting

76 (56)

M12

E5

Battery (−)

4 – 2 bolt mounting

76 (56)

M12

DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 4 FI−UPM)

E4

Battery (+)

4 – 2 bolt mounting

76 (56)

M12

E5

Battery (−)

4 – 2 bolt mounting

76 (56)

M12

Input and Output Neutral

E12

Neutral

12 – 2 bolt mounting

22 (16)

M10

Customer Ground

Ground

Ground

15 – 1 bolt mounting

22 (16)

M10

NOTE Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed in Table 3-13 on page 3−15.