INTERFACE AND CONTROL WIRING

INSTALLATION NOTES AND

TERMINAL LOCATIONS

063006

D

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

164201546---7

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS Sidecar Installation and Operation Manual

S 164201586 Rev E www.powerware.com

A-64

1.

Use Class 1 wiring methods (as defined by the NEC) for control wiring. The wire should be

rated at 600 volts, 1A minimum and 12 AWG maximum. Use twisted–pair wires for each

input and common. All control wiring is customer-supplied.

2.

When installing auxiliary contact control wiring between the UPS Sidecar and a remotely

located UPM 2 interface terminals, conduit must be installed between the UPM and the

UPS Sidecar. Install the control wiring in separate conduit from the power wiring.

3.

Alarms display as Building Alarm 1 and Building Alarm 2 on the UPS Control Panel Display

Screen, unless the alarms are programmed to display the alarm functional name.

4.

Refer to Table R, the following sheets of this drawing, Drawing 164201546---6, sheet

11 of 34 through sheet 20 of 34, and to Chapter 2 for customer interface and control wiring

for parallel redundant configurations.

Table R. TB1 Terminals – 1+1 Parallel Redundant Configuration

UPS

Sidecar

Terminal

TB1

Name

Description

1

Not Used

2

Not Used

3

MOB 1 Aux 1 Contact NC

Contacts used to indicate whether UPS Sidecar

MOB 1 is closed. Contacts are open when MOB 1

is closed.

4

MOB 1 Aux 1 Contact Common

5

MOB 1 Aux 2 Contact NO

Contacts used for backup control (pull chain) for

parallel operation.

6

MOB 1 Aux 2 Contact Common

7

MOB 2 Aux 1 Contact NC

Contacts used to indicate whether UPS Sidecar

MOB 2 is closed. Contacts are open when MOB 2

is closed.

8

MOB 2 Aux 1 Contact Common

9

MOB 2 Aux 2 Contact NO

Contacts used for backup control (pull chain) for

parallel operation.

10

MOB 2 Aux 2 Contact Common