Powerware UPS Sidecar Powerware 9390 User Manual

Page 72

Advertising
background image

POWER WIRING INSTALLATION NOTES

092107

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

D

164201546---4

6 of 10

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS Sidecar Installation and Operation Manual

S 164201586 Rev E www.powerware.com

A-22

Table I. UPS Sidecar Maintenance Bypass Power Cable Terminations

80/40, 80/50, 80/60, 80/80, 208/208V and 160/100, 160/120, 160/160, 480/480V

Terminal Function

Function

Size of Pressure

Termination

Tightening Torque

Nm (lb in)

Type

Screw

AC Input to Maintenance

Bypass or Optional BIB

Phase A 1 --- 2/0---250 kcmil

1 --- 2/0---500 kcmil

31.1 (275)

31.1 (275)

5/16” Hex

3/8” Hex

Phase B 1 --- 2/0---250 kcmil

1 --- 2/0---500 kcmil

31.1 (275)

31.1 (275)

5/16” Hex

3/8” Hex

Phase C 1 --- 2/0---250 kcmil

1 --- 2/0---500 kcmil

31.1 (275)

31.1 (275)

5/16” Hex

3/8” Hex

AC Input to Optional RIB

Phase A 1 --- 2/0---250 kcmil

1 --- 2/0---500 kcmil

31.1 (275)

31.1 (275)

5/16” Hex

3/8” Hex

Phase B 1 --- 2/0---250 kcmil

1 --- 2/0---500 kcmil

31.1 (275)

31.1 (275)

5/16” Hex

3/8” Hex

Phase C 1 --- 2/0---250 kcmil

1 --- 2/0---500 kcmil

31.1 (275)

31.1 (275)

5/16” Hex

3/8” Hex

AC Output to Critical Load Phase A 1 --- 2/0---250 kcmil

1 --- 2/0---500 kcmil

31.1 (275)

31.1 (275)

5/16” Hex

3/8” Hex

Phase B 1 --- 2/0---250 kcmil

1 --- 2/0---500 kcmil

31.1 (275)

31.1 (275)

5/16” Hex

3/8” Hex

Phase C 1 --- 2/0---250 kcmil

1 --- 2/0---500 kcmil

31.1 (275)

31.1 (275)

5/16” Hex

3/8” Hex

Table J. UPS Sidecar 1+1 Parallel Redundant Power Cable Terminations

40/20, 40/30, 40/40, 208/208V and 80/40, 80/50, 80/60, 80/80, 480/480V

Terminal Function

Function

Size of Pressure

Termination

Tightening Torque

Nm (lb in)

Type

Screw

AC Input from UPM2 to

MOB 2 (standalone

installation)

Phase A 1 --- #4---350 kcmil

20.3 (180)

3/16” Hex

Phase B 1 --- #4---350 kcmil

20.3 (180)

3/16” Hex

Phase C 1 --- #4---350 kcmil

20.3 (180)

3/16” Hex

AC Output to Critical Load

(without SLB) Terminal

Block

Phase A 1 --- #14---2/0

13.5 (120)

3/16” Hex

Phase B 1 --- #14---2/0

13.5 (120)

3/16” Hex

Phase C 1 --- #14---2/0

13.5 (120)

3/16” Hex

AC Output to Critical Load

(with SLB)

Phase A 1 --- #4---350 kcmil

20.3 (180)

3/16” Hex

Phase B 1 --- #4---350 kcmil

20.3 (180)

3/16” Hex

Phase C 1 --- #4---350 kcmil

20.3 (180)

3/16” Hex

Neutral (80/480)

Neutral

4 --- #14---1/0

5.6 (50)

Slotted

Neutral (40/208)

Neutral

8 --- #6---250 kcmil

42.4 (375)

5/16” Hex

Ground

Ground

2 --- #14---1/0

5.6 (50)

Slotted

Advertising