Powerware UPS Sidecar Powerware 9390 User Manual

Page 66

Advertising
background image

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

031505

A

OUTPUT TO

CRITICAL LOAD

E4. E5

FUSE

K5

STATIC

SWITCH

FUSE

K3

FUSE

BATTERY

CONVERTER

RECTIFIER

INVERTER

K1

UPM 2

E1

E2

E3

E6

E7

E8

E12

A

B

SEE NOTE 2

UPS Sidecar

E4. E5

FUSE

K5

STATIC

SWITCH

FUSE

K3

FUSE

BATTERY

CONVERTER

RECTIFIER

INVERTER

K1

UPM 1

E1

E2

E3

E6

E7

E8

E12

A

B

SEE NOTE 2

TYPICAL PARALLEL REDUNDANT SYSTEM

(1+1 CONFIGURATION)

*

*

*

*

C

NOTE

1. UPM and system bypass input feeds

must come from the same source.

2. Remove jumper for dual-feed.

3. If the load requires a neutral, a bypass

neutral feeder must be supplied.

MOB 1

MOB 2

SLB

(OPTIONAL)

D

BATTERY

BREAKER

BATTERY

CABINET

BATTERY

BREAKER

BATTERY

CABINET

UPS SIDECAR ONELINE DRAWINGS
164201546---3

C

11 of 11

E9, E10, E11

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS Sidecar Installation and Operation Manual

S 164201586 Rev E www.powerware.com

A-16

A ---

AC Input to UPS Rectifier (dual-feed)

B ---

AC Input to UPS Rectifier (single-feed) and Bypass (single- and dual-feed)

C --- DC Input from Battery
D --- Output to Critical Load
* ---

Overcurrent Protection Provided by Others