UPS SIDECAR FEATURES, CONTROLS, AND OPERATION

EATON Powerware

®

9390 UPS Sidecar Installation and Operation Manual

S 164201586 Rev E www.powerware.com

4-13

4.5

UPS Sidecar Operation – Maintenance Bypass Configuration

4.5.1

Using the UPS when a UPS Sidecar is Installed

NOTE Before starting the UPS with the UPS Sidecar, verify all installation tasks are complete and a
preliminary startup has been performed by authorized service personnel. The preliminary startup verifies all
electrical interconnections to confirm the installation was successful and the UPS operates properly.

1.

Remove the screw securing the bottom of the UPS Sidecar front panel. Lift up
the panel and remove.

2.

Verify that the UPS Sidecar circuit breakers and switches are set as follows:

MBP

OPEN

MIS

CLOSED

BIB (if installed)

CLOSED

RIB (if installed)

CLOSED

3.

Reinstall the UPS Sidecar front panel and secure with the screw at the bottom of
the panel.

4.

Start the UPS in Normal mode according to the instructions in the operation
chapter of the applicable Powerware 9390 installation and operation manual,
listed in paragraph 1.5.

4.5.2

Transferring the UPS to Maintenance Bypass

C A U T I O N

Only trained personnel familiar with the operation of this equipment should transfer loads. Failure to follow
this transfer sequence may cause loss of power to loads or overload protection devices to activate.

C A U T I O N

In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities.

1.

Press the CONTROLS pushbutton on the main menu bar. The System Controls
screen appears.

2.

Press the BYPASS pushbutton on the System Controls menu bar.

The UPS transfers to Bypass mode and the critical load is immediately supplied
by the bypass source. If the bypass source is not available, the power processor
remains on and an alarm sounds.

3.

Verify that the BYPASS status indicator is illuminated, indicating the UPS is
operating in Bypass mode.

4.

Press the

pushbutton on the System Controls screen to display System

Controls Screen 2.

5.

Press the PM OFF pushbutton on the System Controls menu bar.

The PM status indicates SHUTDOWN

.

The input and output contactors open, the

battery breaker or disconnect is tripped, and the power module is turned off. The
bypass source supplies the critical load.