POWER WIRING INSTALLATION NOTES

063006

B

164201546---4

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

10 of 10

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS Sidecar Installation and Operation Manual

S 164201586 Rev E www.powerware.com

A-26

16.

The MIS and SLB breakers on the 80 kVA, 120 kVA, and 160 kVA UPS Sidecars are

adjustable trip breakers and are set to maximum at the factory. During installation these

breakers must be adjusted for the site requirements using the dial on each breaker. The

MIS and SLB breakers on the 40 kVA UPS Sidecar are non-adjustable.

17.

The continuous current (Ir) values for the corresponding lettered adjustment setting

marked on the MIS and SLB breakers are listed in Table Q.

Table Q. MIS and SLB Continuous Current (Ir) Settings

Breaker

Setting

80 kVA Continuous

Current (Ir)

120 kVA Continuous

Current (Ir)

160 kVA Continuous

Current (Ir)

208V

480V

208V

480V

208V

480V

A

250

100

N/A

100

N/A

250

B

300

125

N/A

125

N/A

300

C

350

150

N/A

150

N/A

350

D

400

160

N/A

160

N/A

400

E

175

N/A

175

N/A

F

200

N/A

200

N/A

G

225

N/A

225

N/A

H

250

N/A

250

N/A