POWER WIRING INSTALLATION NOTES

092107

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

E

164201546---4

7 of 10

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS Sidecar Installation and Operation Manual

S 164201586 Rev E www.powerware.com

A-23

Table K. UPS Sidecar 1+1 Parallel Redundant Power Cable Terminations

120/100, 120/120 kVA 480/480V

Terminal Function

Function

Size of Pressure

Termination

Tightening Torque

Nm (lb in)

Type

Screw

AC Input from UPM2 to

MOB 2 (standalone

installation)

Phase A 1 --- #4---350 kcmil

20.3 (180)

3/16” Hex

Phase B 1 --- #4---350 kcmil

20.3 (180)

3/16” Hex

Phase C 1 --- #4---350 kcmil

20.3 (180)

3/16” Hex

AC Output to Critical Load

(without SLB)

Phase A 1 --- #6---500 kcmil

56.5 (500)

1/2 Hex

Phase B 1 --- #6---500 kcmil

56.5 (500)

1/2 Hex

Phase C 1 --- #6---500 kcmil

56.5 (500)

1/2 Hex

AC Output to Critical Load

(with SLB)

Phase A 1 --- #4---350 kcmil

20.3 (180)

3/16” Hex

Phase B 1 --- #4---350 kcmil

20.3 (180)

3/16” Hex

Phase C 1 --- #4---350 kcmil

20.3 (180)

3/16” Hex

Neutral

Neutral

8 --- #6---250 kcmil

42.4 (375)

5/16” Hex

Ground

Ground

4 --- #14---1/0

5.6 (50)

Slotted

Table L. UPS Sidecar 1+1 Parallel Redundant Power Cable Terminations

80/40, 80/50, 80/60, 80/80 kVA 208/208V

Terminal Function

Function

Size of Pressure

Termination

Tightening Torque

Nm (lb in)

Type

Screw

AC Input from UPM2 to

MOB 2 (standalone

installation)

Phase A 1 --- 2/0---250 kcmil

1 --- 2/0---500 kcmil

31.1 (275)

31.1 (275)

5/16” Hex

3/8” Hex

Phase B 1 --- 2/0---250 kcmil

1 --- 2/0---500 kcmil

31.1 (275)

31.1 (275)

5/16” Hex

3/8” Hex

Phase C 1 --- 2/0---250 kcmil

1 --- 2/0---500 kcmil

31.1 (275)

31.1 (275)

5/16” Hex

3/8” Hex

AC Output to Critical Load

(without SLB)

Phase A 1 --- 2/0---250 kcmil

1 --- 2/0---500 kcmil

31.1 (275)

31.1 (275)

5/16” Hex

3/8” Hex

Phase B 1 --- 2/0---250 kcmil

1 --- 2/0---500 kcmil

31.1 (275)

31.1 (275)

5/16” Hex

3/8” Hex

Phase C 1 --- 2/0---250 kcmil

1 --- 2/0---500 kcmil

31.1 (275)

31.1 (275)

5/16” Hex

3/8” Hex

AC Output to Critical Load

(with SLB)

Phase A 1 --- 2/0---250 kcmil

1 --- 2/0---500 kcmil

31.1 (275)

31.1 (275)

5/16” Hex

3/8” Hex

Phase B 1 --- 2/0---250 kcmil

1 --- 2/0---500 kcmil

31.1 (275)

31.1 (275)

5/16” Hex

3/8” Hex

Phase C 1 --- 2/0---250 kcmil

1 --- 2/0---500 kcmil

31.1 (275)

31.1 (275)

5/16” Hex

3/8” Hex

Neutral

Neutral

8 --- #6---250 kcmil

42.4 (375)

5/16” Hex

Ground

Ground

4 --- #14---1/0

5.6 (50)

Slotted

13.

Conduit is to be sized to accommodate one neutral conductor the same size as the phase

conductor and one #8 AWG ground conductor. If two neutral conductors or an oversized

neutral conductor are to be installed, size the conduit to accommodate the extra wire or

size. All Powerware 9390 products can accommodate a double-sized neutral.

14.

External UPS Sidecar rectifier and bypass input overcurrent protection is not provided by

this product, but is required by codes. Refer to Table B through Table E for wiring

requirements.