Chapter 3 understanding operation, 1 maintenance bypass configuration, 1 ups mode – Powerware UPS Sidecar Powerware 9390 User Manual

Page 31

Advertising
background image

EATON Powerware

®

9390 UPS Sidecar Installation and Operation Manual

S 164201586 Rev E www.powerware.com

3-1

Chapter 3

Understanding Operation

The UPS Sidecar can be configured for either maintenance bypass or parallel
redundant operation.

3.1

Maintenance Bypass Configuration

3.1.1

UPS Mode

When the Maintenance Bypass switch (MBP) is open and the Maintenance Isolation
switch (MIS) is closed, conditioned and protected power from the UPS is routed
through the MIS to the critical load.

If the optional Bypass Input Breaker (BIB) is installed, power is supplied to the UPS
through the BIB, and the UPS rectifier and bypass input terminals are jumpered
together. If the optional BIB and Rectifier Input Breaker (RIB) are installed, the UPS
rectifier is supplied power through the RIB and the UPS bypass is supplied power
through the BIB, for a dual-feed system. In a single-feed system, the BIB and RIB
input terminals are jumpered together and power is supplied to the UPS rectifier and
bypass input terminals from a single source.

Figure 3-1 shows the path of electrical power through the UPS Sidecar when
operating in UPS mode.

AC INPUT

TO UPS

OUTPUT TO

CRITICAL LOAD

UPS SIDECAR

RIB

(OPTIONAL)

BIB

(OPTIONAL)

MIS

MBP

AC INPUT

TO BYPASS

TO UPS RECTIFIER

INPUT

FROM UPS OUTPUT

TO UPS BYPASS

INPUT

MAIN POWER FLOW IN UPS MODE

MAIN POWER FLOW IN MAINTENANCE BYPASS MODE

Figure 3-1. Path of Current Through the UPS Sidecar in UPS Mode