Powerware UPS Sidecar Powerware 9390 User Manual

Page 69

Advertising
background image

POWER WIRING INSTALLATION NOTES

092107

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

D

164201546---4

3 of 10

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS Sidecar Installation and Operation Manual

S 164201586 Rev E www.powerware.com

A-19

Table D. INPUT/OUTPUT Ratings & External Wiring Requirements for

Powerware 9390 UPS Sidecar (1+1 Parallel Redundant) 208V

Units

Rating 50/60 Hz

Basic Unit Rating

UPS kVA

40

50

60

80

Input and Bypass Input

Output

VOLTS

VOLTS

208
208

208
208

208
208

208
208

AC Input from UPM

Full Load Current for each Module

(3) Phases, (1) Neutral---if required, (1) Ground

AMPS

111

139

167

222

Minimum Conductor Size for each Module
Number per Phase for each Module

For customer-supplied wiring in a standalone
installation, refer to the applicable Powerware 9390
installation and operation manual, listed in paragraph

1.5, for wire size. Wiring for line-up-and-match
installation is factory-supplied.

AC Output to Critical Load

Full Load Current

(3) Phases, (1) Neutral---if required, (1) Ground

D

AMPS

111

139

167

222

Minimum Conductor Size

Number per Phase

AWG or kcmil

(each)

2/0

(1)

4/0

(1)

250

(1)

2/0

(2)

NOTE Callout letter

D

maps to drawing 164201546---3, sheet 11 of 11.

Table E. INPUT/OUTPUT Ratings & External Wiring Requirements for

Powerware 9390 UPS Sidecar (1+1 Parallel Redundant) 480V

Units

Rating 50/60 Hz

Basic Unit Rating

UPS

kVA

20

(See

Note 2)

30

(See

Note 2)

40

50

60

80

100

120

160

Input and Bypass Input

Output

VOLTS

VOLTS

480
480

480
480

480
480

480
480

480
480

480
480

480
480

480
480

480
480

AC Input from UPM

Full Load Current for each Module

(3) Phases, (1) Neutral---if required,
(1) Ground

AMPS

48

48

48

60

72

96

120

144

192

Minimum Conductor Size for each
Module

Number per Phase for each Module

For customer-supplied wiring in a standalone installation, refer to the applicable
Powerware 9390 installation and operation manual, listed in paragraph 1.5, for wire
size. Wiring for line-up-and-match installation is factory-supplied.

AC Output to Critical Load

Full Load Current

(3) Phases, (1) Neutral---if required,
(1) Ground

D

AMPS

48

48

48

60

72

96

120

144

192

Minimum Conductor Size

Number per Phase

AWG or

kcmil

(each)

4

(1)

4

(1)

4

(1)

2

(1)

1

(1)

1/0

(1)

4/0

(1)

4/0

(1)

1/0

(2)

NOTE 1. Callout letter

D

maps to drawing 164201546---3, sheet 11 of 11.

NOTE 2. 40/20 kVA and 40/30 kVA parallel systems must be wired same as a 40/40 kVA.

Advertising