2 parallel redundant configuration, 1 ups sidecar standard features, 2 maintenance bypass mode with ups sidecar – Powerware UPS Sidecar Powerware 9390 User Manual

Page 32

Advertising
background image

UNDERSTANDING OPERATION

EATON Powerware

®

9390 UPS Sidecar Installation and Operation Manual

S 164201586 Rev E www.powerware.com

3-2

3.1.2

Maintenance Bypass Mode with UPS Sidecar

An MBP is used to safely supply utility power to the critical load during periods of
UPS maintenance or repairs. The bypass source supplies the commercial AC power
to the load directly.

When the MBP is closed, the load is wrapped around the UPS while power is still
supplied to the load by the UPS through the MIS. The MIS is then opened, isolating
the UPS from the Bypass power source. The UPS can be safely shut down and power
removed from the UPS without interrupting power to the critical load. If the optional
BIB and RIB are installed, the BIB and RIB are opened to remove power from the
UPS. Otherwise, external upstream breakers are used to remove power. The UPS
now can be serviced or replaced safely.

The critical load is not protected while the UPS is in Maintenance Bypass mode.

Figure 3-2 shows the path of electrical power through the UPS Sidecar when
operating in Maintenance Bypass mode.

AC INPUT

TO UPS

OUTPUT TO

CRITICAL LOAD

UPS SIDECAR

RIB

(OPTIONAL)

BIB

(OPTIONAL)

MIS

MBP

AC INPUT

TO BYPASS

TO UPS RECTIFIER

INPUT

FROM UPS OUTPUT

TO UPS BYPASS

INPUT

MAIN POWER FLOW IN UPS MODE

MAIN POWER FLOW IN MAINTENANCE BYPASS MODE

Figure 3-2. Path of Current Through the UPS Sidecar in Maintenance Bypass Mode

3.2

Parallel Redundant Configuration

Refer to the applicable Powerware 9390 installation and operation manual, listed in
paragraph 1.5, for parallel theory of operation.

Advertising