UPS SIDECAR ONELINE DRAWINGS

092107

C

MAINTENANCE BYPASS WITH BIB AND RIB

80/40, 80/50, 80/60, 80/80 kVA, 480/480V,

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

K1

K5

K3

Powerware 9390 UPS CABINET

UPS Sidecar

MAINTENANCE

BYPASS SWITCH

(MBP)

AC INPUT

TO BYPASS

B

MAINTENANCE

ISOLATION SWITCH

(MIS)

BYPASS INPUT

BREAKER (BIB)

RECTIFIER INPUT

BREAKER (RIB)

AC INPUT

TO UPS

E4. E5

A

SINGLE-FEED

JUMPER

(REMOVE FOR

DUAL-FEED)

C

AC OUTPUT

TO

CRITICAL LOAD

BATTERY

CONVERTER

INVERTER

RECTIFIER

NOTE

1. Remove jumper for dual-feed.

2. For 80kVA 480/480V dual-feed, move

BIB wires from E1, E2, E3 to E6, E7, E8.

3. If the load requires a neutral, a bypass

neutral feeder must be supplied.

164201546---3

10 of 11

E6, E7, E8

E9, E10, E11

E1, E2, E3

(RELOCATE F

TO HERE OR

DUAL-FEED)

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS Sidecar Installation and Operation Manual

S 164201586 Rev E www.powerware.com