Omega RD260A User Manual

Page 95

Advertising
background image

8 - 5

8. TROUBLESHOOTING

Is the input free of noise?

NO

YES

¥ Separate the input/communication

signal wires from the noise source.

¥ Ground the recorder.

¥ Use shielded cable for input/

communication signal.

¥ Attach an insulation transformer for

the power line.

¥ Use a power line filter.

¥ When an inductive load is used in the

alarm output line, insert a surge

suppressor into this line.

Contact OMEGA Engineering.

Glitch is found other than the previously mentioned ploblems.