To specify a ber test – Telect MIX 56 User Manual

Page 97

Advertising
background image

MIX 56 User Manual

4 Software Operation

122188-10 A0

Telect, Inc.

4-51

When test mode “T1/E1 Test on High Speed Line” is selected then you also
specify:

1.

Which channel of the muxed DS3 signal to insert the test pattern
on.

2.

Whether to use a framed test signal or not.

3.

What frame format to use if using a framed test signal.

4.

What remote alarm format to use if T1 line and using a framed test
signal

When test mode “Unframed Test on Low Speed Line” is selected then you
also specify which low speed channel to do the test on.

To Specify a BER Test

Step

Action

1.

From the Directory screen, press 20 to select “BER Testing”, then
press enter. The “BER Testing” screen appears:

2.

In the “Mode” field select the mode by pressing the spacebar to tog-
gle between “CBit DS3 Test on High Speed Line”, “Unframed Test
on Low Speed Line”, or “T1/E1 Test on High Speed Line” and then
pressing Enter.

MIX 56 by Telect MIX 56 Directory (CTRL+D)

Help (?)

BER Testing

-----------

Mode: T1/E1 Test on High Speed Line

Pattern: Disabled

Receiving Pattern: None

Low Speed Channel #: 1 Line Type: T1

Framed Signal: Yes

Frame Format: ESF

RAI: FS Bit

[Apply]