Chapter 1 general information – TDK GENESYS 1500W User Manual

Page 14

Advertising
background image

83-507-013 Rev. D

6

CHAPTER 1 GENERAL INFORMATION

1.1 USER MANUAL CONTENT

This User’s Manual contains the operating instructions, installation instructions and specifications of
the Genesys

TM

1500W and 750W power supply series. The instructions refer to the standard power

supplies, including the built-in RS232/RS485 serial communication. For information related to opera-
tion with the optional IEEE programming, refer to User’s Manual for Power Supply Programming In-
terface. (TDK-Lambda Americas Inc. P/N 83-030-200)

1.2 INTRODUCTION

1.2.1

General Description

Genesys

TM

power supplies are wide output range, high performance switching power supplies. The

Genesys

TM

series is power factor corrected and operates from worldwide AC voltage range continu-

ously. Output Voltage and Current are continuously displayed and LED indicators show the complete
operating status of the power supply. The Front panel controls allow the user to set the output pa-
rameters, the protections levels (Over-Voltage protection, Under-Voltage limit and Foldback) and pre-
view the settings. The rear panel includes the necessary connectors to control and monitor the power
supply operation by remote analog signals or by the built-in serial communication (RS232/RS485).
GPIB programming and Isolated-Analog programming/monitoring are optional.

1.2.2

Models covered by this Manual

Model

Voltage
range (V)

Current
range (A)

Model

Voltage
range (V)

Current
range (A)

GEN 6-100

0 - 6

0 - 100

GEN 60-12.5

0 - 60

0 - 12.5

GEN 6-200

0 - 6

0 - 200

GEN 60-25

0 - 60

0 - 25

GEN 8-90

0 - 8

0 - 90

GEN 80-9-5

0 - 80

0 - 9.5

GEN 8-180

0 - 8

0 - 180

GEN 80-19

0 - 80

0 - 19

GEN 12.5-60

0 - 12.5

0 - 60

GEN 100-7.5

0 - 100

0 - 7.5

GEN 12.5-120

0 - 12-5

0 - 120

GEN 100-15

0 - 100

0 - 15

GEN 20-38

0 - 20

0 - 38

GEN 150-5

0 - 150

0 - 5

GEN 20-76

0 - 20

0 - 76

GEN 150-10

0 - 150

0 - 10

GEN 30-25

0 - 30

0 - 25

GEN 300-2.5

0 - 300

0 - 2.5

GEN 30-50

0 - 30

0 - 50

GEN 300-5

0 - 300

0 - 5

GEN 40-19

0 - 40

0 - 19

GEN 600-1.3

0 - 600

0 - 1.3

GEN 40-38

0 - 40

0 - 38

GEN 600-2.6

0 - 600

0 - 2.6

GEN 50-30

0 - 50

0 - 30

Table 1-1: Models covered by the Manual

1.2.3

Features and options

 Constant Voltage / Constant Current with automatic crossover.

 Active power factor correction.

 Universal Input Voltage (85265Vac), continuous operation.

 Embedded Microprocessor Controller.

 Built-in RS-232/RS-485 Interface.

 Voltage & Current high resolution adjustment by digital encoders.

 High accuracy programming/readback.

 Software Calibration (no internal trimmers / potentiometers).

 Last Setting Memory.

 Independent Remote ON/OFF (opto-isolated) and remote Enable/Disable.

 Parallel operation (Master/Slave) with Active current sharing.