TDK GENESYS 1500W User Manual

Page 27

Advertising
background image

83-507-013 Rev. D

19

CAUTION

When local sensing, a short from +LS or +S to -V or -S or -LS,
will cause damage to the power supply. Reversing the sense
wires might cause damage to the power supply in local and
remote sensing. (Do not connect -S to +V or +S to -V).

2. Wire size should be selected to enable voltage drop per lead to be less than 1.0V at the rated

current. Although units will compensate for up to 5V in each load wire, it is recommended to
minimize the voltage drop (1V typical maximum) to prevent excessive output power consump-
tion from the power supply and poor dynamic response to load changes. Please refer to Ta-
bles 3-2 and 3-3 for minimum wire length (to limit voltage drop) in American and European di-
mensions respectively.

Maximum length in Feet to limit

voltage drop to 1V or less

Wire size

AWG

Resistivity

OHM/1000ft

5A

10A

20A

50A

150A

14

2.526

80

40

20

8

2

12

1.589

120

60

30

12

3.4

10

0.9994

200

100

50

20

6

8

0.6285

320

160

80

32

10

6

0.3953

500

250

125

50

16

4

0.2486

800

400

200

80

26

2

0.1564

1200

600

300

125

40

0

0.0983

2000

1000

500

200

68

Table 3-2: Maximum wire length for 1V drop on lead (in feet)

Maximum length in meters to limit

voltage drop to 1V or less

Cross sect.

area

(mm²)

Resistivity

OHM/Km

5A

10A

20A

50A

150A

2.5

8.21

24.0

12.0

6.0

2.4

0.8

4

5.09

39.2

18.6

9.8

4.0

1.4

6

3.39

59.0

29.4

14.8

5.8

2.0

10

1.95

102.6

51.2

25.6

10.2

3.4

16

1.24

160.0

80.0

40.0

16.0

5.4

25

0.795

250.0

125.0

62.0

25.2

8.4

35

0.565

354.0

177.0

88.0

35.4

11.8

Table 3-3: Maximum wire length for 1 V drop on lead (in meters)

For currents not shown in Table 3-2 and 3-3, use the formula:

Maximum length=1000/(current x resistivity)

Where current is expressed in Amperes and resistivity in ohms/km or ohms/1000ft.

3.9.3

Wire termination

The wires should be properly terminated with terminals securely attached. DO NOT use unterminated
wires for load connection at the power supply.

Advertising
This manual is related to the following products: